1750
Operators Manual
Specifications for the System: Recorder and Power Analyze Software
General Specifications
Power Quality Measurement Standards |
|
Conformance | IEC |
| IEEE1459, IEC |
Clock/Calendar | Leap years, |
Not more than ± 1 s/day | |
Internal Memory Capacity for Data | At least 2 GB |
Maximum Recording Period | At least 31 days |
Measurement Time Control | Automatic |
Maximum Number of Events | Limited only by the size of the internal memory. |
Power Requirements | 100 to 240 V rms ± 10 %, |
Operating Time During Interruptions |
|
(internal UPS operation) | 5 minutes per interruption, 60 minutes total operating time without |
| recharging |
Dimensions | 215 x 310 x 35 mm (8.5 x 12.2 x 3.5 inch) |
Mass (Weight) | 6.3 kg (14 lbs) |
Input Specifications
Measurement Types | One Phase Plus Neutral, One Phase IT No Neutral, One Phase Split |
| Phase, Three Phase Wye, Three Phase Delta, Three Phase IT, Three |
| Phase High Leg, Three Phase Open Leg, 2 Element Delta, 2 ½ |
| Element Wye |
Input Channels | Voltage: 5 channels, AC/DC Current: 5 channels |
Voltage Channels | Input resistance: 2 MΩ |
| Input capacitance: <20 pF |
Current Channels | |
| Types available: current clamps, |
Measuring Method | Simultaneous digital sampling of voltage and current. Digital PLL |
| synchronized sampling, internal frequency reference used during |
| voltage drops. |
Synchronization and Sampling
The PLL synchronizes to the | |
| and to the |
| types can be characterized as either wye or delta. |
PLL Lock Range | 42.5 to 69 Hz |
Sampling Frequency | Voltage and current: 256 samples/cycle |
| |
| 3072 points/12 cycles (60 Hz) |
| Transient Voltage: 5 MHz |
A/D Resolution | Voltage and current: 24 bits |
| Transient voltage: 14 bits |
Voltage and Current Measurements
Voltage Measurement Range | AC voltage: 1000 V rms ± 10 % Overrange |
| DC voltage: ± 1000 V + 10 % Overrange |
Voltage Crest Factor | 3 or less |
Voltage Input Impedance | 2 MΩ |
Current Measurement Range | Depends on current probe used |
Current Crest Factor | 4 or less |
Current Input Characteristics | 2 V rms = full scale, 1 MΩ Input Impedance for ferro CTs, low |
| impedance for |
50