4.Press Sonde Depth [SK] to read ADP Depth
−− The depth to the ADP is displayed in units, as specified in the receiver set up menu.
−− Five Sonde depth readings can be saved with the time and date measured. Press Mem Select [SK] after the Sonde depth displays.
−− Press Mem Select [SK] to select a specific memory location
5.Press Clear All [SK] to delete all saved depth readings.
6.Press Mem Select [SK] to select the memory location to store the depth readings.
7.When the preferred location appears on the display, press Save [SK]. The display and memory location will populate with the current information.
8.Each memory location can be reviewed by pressing Mem Select [SK].
9.Press Cable Depth [SK] to switch to the cable depth display, or Locate/OK [5] to return to Locate Mode.
Note: During a depth measurement, the display will exhibit ‘-
12.Locating Buried Sheath Faults and Earth Return Faults
(3M™ Dynatel™ Models 2273M and
Note: Remove (disconnect) both the
Note: This method only works on direct buried cables/conductors. It will not work if the cables/conductors are faulted inside of a conduit, such as a PVC conduit.
A. Transmitter Setup
Note: Do not make any connections while the transmitter is on.
1.Attach the red clip to the
2.Place the ground rod behind the transmitter and in parallel with the target path.
3.Connect the black clip to the ground rod behind the transmitter and in parallel with the target path.
4.Press and hold off
36 |
|