Sample Configurations

Sample #1

The user would like to control 4 boilers. Each boiler is controlled from the same Water Temperature sensor but at a different temperature reading. Once a boiler is activated it must remain on at least 5 minutes and if a boiler is de-activated it must remain off at least 10 minutes. Additionally, the boilers are locked out when the Outdoor Air Temperature is above 65°F.

Analog Input #1 Configured as Thermister Type III Sensor

Note that some Hi and Lo alarm limits were set and that the reading is in degrees Fahrenheit.

20

Image 26
Contents GPC Plus Controller Page OE331-21-GPC OE331-21-GPCPLUS +VDC AIN1 Page Main Status Screen General Purpose ControllerDescription Analog Inputs Relays Analog Outputs Week Schedules & Holidays Analog Input Configurations Page Page RH% Wall Sensor Slide Offset Optimal Start Temperatures Push-Button OverrideAnalog Input #6 Relay Output Configuration Control MethodsReset Source Limits Control/Reset SourcesDelay & Run Times Enabling RelayAND/OR Conditional Tests Controlling Setpoint DeadbandControlling Schedule Global Binary Channel Run Time AlarmRelay Output Type Lead/Lag ControlVentilation Control Analog Output Configuration Possible Control ModesPID Control Possible Control SourcesFloating Point Control Alternate Override Proportional Reset SignalEconomizer Control Lead/Lag Pump VFD Control Sample Configurations Sample #1Page Page Relay Output #2 Programming Used for Boiler #1 Relay Output #3 Programming Used for Boiler #2 Relay Output #4 Programming Used for Boiler #3 Relay Output #5 Programming Used for Boiler #4 Operation Page Sample #2 Page Page Page Main Status Screen Failure Mode Page