Relay Output #4 Programming ( Used for Boiler #3 )

The third boiler stage is enabled to operate if the water temperature is below 160°F and will remain on until it rises to 175°F. The third stage can only operate if the second boiler stage relay #3 has been active for at least 5 minutes. Once activated, this stage must remain on for 5 minutes and once de-activated it must remain off for 10 minutes.

25

Image 31
Contents GPC Plus Controller Page OE331-21-GPC OE331-21-GPCPLUS +VDC AIN1 Page Description General Purpose ControllerMain Status Screen Analog Inputs Relays Analog Outputs Week Schedules & Holidays Analog Input Configurations Page Page RH% Wall Sensor Slide Offset Push-Button Override Optimal Start TemperaturesAnalog Input #6 Control Methods Relay Output ConfigurationEnabling Relay Control/Reset SourcesDelay & Run Times Reset Source LimitsControlling Schedule Controlling Setpoint DeadbandAND/OR Conditional Tests Lead/Lag Control Run Time AlarmRelay Output Type Global Binary ChannelVentilation Control Possible Control Modes Analog Output ConfigurationFloating Point Control Possible Control SourcesPID Control Economizer Control Proportional Reset SignalAlternate Override Lead/Lag Pump VFD Control Sample #1 Sample ConfigurationsPage Page Relay Output #2 Programming Used for Boiler #1 Relay Output #3 Programming Used for Boiler #2 Relay Output #4 Programming Used for Boiler #3 Relay Output #5 Programming Used for Boiler #4 Operation Page Sample #2 Page Page Page Main Status Screen Failure Mode Page