Orion Car Audio OE331-21 manual Wall Sensor Slide Offset

Page 14

Wall Sensor Slide Offset

If you have configured a specific input to be connected to one of WattMasters’ standard OE212 or OE213 Flush Mount Wall Sensors which contain the optional slide offset, be sure to enter a value for “Maximum Slide Offset Effect”. This tells the controller how much effect to have on the selected setpoints when the slide is fully deflected up or down. When the slide is in the “center” position, it has no effect on the current setpoints.

Note: There are separate outputs on the Flush Mount Wall Sensors for measuring the room temperature and reading the slide offset. Be sure to configure the correct input for the slide offset and do not use the temperature signal coming from the wall sensor for this option.

The slide offset is normally used by one or more relay outputs, configured to “look” at this value and include its effect on their normal setpoints.

As you can see on the sample screen, Relay #4 is set to activate if the LoadTemp rises above 72.0°F. It is also monitoring the Sensor Slide Adjust input on Analog Input #5. If the slide is pushed up, the Hi Limit Setpoint will rise to 74.0°F and the Lo Limit Setpoint

8

Image 14
Contents GPC Plus Controller Page OE331-21-GPC OE331-21-GPCPLUS +VDC AIN1 Page Main Status Screen General Purpose ControllerDescription Analog Inputs Relays Analog Outputs Week Schedules & Holidays Analog Input Configurations Page Page RH% Wall Sensor Slide Offset Optimal Start Temperatures Push-Button OverrideAnalog Input #6 Relay Output Configuration Control MethodsReset Source Limits Control/Reset SourcesDelay & Run Times Enabling RelayAND/OR Conditional Tests Controlling Setpoint DeadbandControlling Schedule Global Binary Channel Run Time AlarmRelay Output Type Lead/Lag ControlVentilation Control Analog Output Configuration Possible Control ModesPID Control Possible Control SourcesFloating Point Control Alternate Override Proportional Reset SignalEconomizer Control Lead/Lag Pump VFD Control Sample Configurations Sample #1Page Page Relay Output #2 Programming Used for Boiler #1 Relay Output #3 Programming Used for Boiler #2 Relay Output #4 Programming Used for Boiler #3 Relay Output #5 Programming Used for Boiler #4 Operation Page Sample #2 Page Page Page Main Status Screen Failure Mode Page