Analog Input #2 Configured as Outdoor Air Thermister Sensor
Notice that we set this reading to broadcast on Global Analog Channel #2. That is because the Outside Air is normally read by one controller on a job and the remaining controllers look at Global Analog #2 for this value, including the GPC Plus. Even if this is the only controller on the job, you must set it to broadcast the outside air so the GPC Plus can “see” what the OA Temperature is.
Analog Input #3 Configured as Not Configured
Analog Input #4 Configured as Not Configured
Analog Input #5 Configured as Not Configured
Analog Input #6 Duct Static Pressure Sensor is not Required
Analog Input #7 Configured as Not Configured