Analog Output
Configuration
Two Proportional Outputs ( 0 - 10 VDC ) are available to the user. This output operates using standard floating point control or a modified Proportional/Derivative control as configured by the user. The controlling setpoint can be reset by any other sensor reading or the outdoor air temperature and the output voltage range can be limited by the user to some range other than the standard 0 - 10 VDC.
Possible Control Modes
0 = Not Configured
1 = Direct Acting Floating Point
2 = Reverse Acting Floating Point
3 = Direct Acting PID
4 = Reverse Acting PID
5 = Relief Pressure Control
6 = Duct Static Pressure Control
16