Orion Car Audio OE331-21 manual Relay Output #3 Programming Used for Boiler #2

Page 30

Relay Output #3 Programming ( Used for Boiler #2 )

The second boiler stage is enabled to operate if the water temperature is below 170°F and will remain on until it rises to 180°F. The second stage can only operate if the first boiler stage relay #2 has been active for at least 5 minutes. Once activated, this stage must remain on for 5 minutes and once de-activated it must remain off for 10 minutes.

24

Image 30
Contents GPC Plus Controller Page OE331-21-GPC OE331-21-GPCPLUS +VDC AIN1 Page General Purpose Controller DescriptionMain Status Screen Analog Inputs Relays Analog Outputs Week Schedules & Holidays Analog Input Configurations Page Page RH% Wall Sensor Slide Offset Optimal Start Temperatures Push-Button OverrideAnalog Input #6 Relay Output Configuration Control MethodsReset Source Limits Control/Reset SourcesDelay & Run Times Enabling RelayControlling Setpoint Deadband Controlling ScheduleAND/OR Conditional Tests Global Binary Channel Run Time AlarmRelay Output Type Lead/Lag ControlVentilation Control Analog Output Configuration Possible Control ModesPossible Control Sources Floating Point ControlPID Control Proportional Reset Signal Economizer ControlAlternate Override Lead/Lag Pump VFD Control Sample Configurations Sample #1Page Page Relay Output #2 Programming Used for Boiler #1 Relay Output #3 Programming Used for Boiler #2 Relay Output #4 Programming Used for Boiler #3 Relay Output #5 Programming Used for Boiler #4 Operation Page Sample #2 Page Page Page Main Status Screen Failure Mode Page