B.2 PID Controller Basics

A pH control loop operates as follows: The pH meter measures the value of the pH in the effluent, and, if the pH is different from the setpoint, the controller actuates the reagent pump (or valve) that adds reagent to a mixing tank. The added reagent adjusts the pH value of the process.

The physical layout of the loop, the sizing of the pump (valve), type of mixing tank, and location of the pH electrodes all have a major impact on the ultimate performance of the loop, after the controller is tuned for optimal performance. The largest single performance factor is the delay time around the loop. This includes the response time of the electrode/meter, time required to deliver the reagent to the process water, time required for the reagent to mix with and react with the process water, and the time required to deliver the completely mixed water to the electrode. If the delay times are too long or the mixing is not complete, the control will be poor regardless of how well the controller is tuned.

The Process pH Meter uses a PID (proportional, integral (reset), derivative (rate) control) control algorithm. Each of the instrument settings along with their effects on the control loop, are described below.

Mode

Manual: The manual output is specified in percent of full-scale PID output (4–20 mA) and is commonly used for testing the output device.

Auto: Allows the process to be controlled automatically using information specified in the Phase, Setpoint, Proportional Band, Integral, and Derivative menus as follows:

Phase

Direct: The control output action will cause the process value to increase.

Reverse: The control output action will cause the process value to decrease.

Setpoint

The setpoint is defined as the desired process value in pH

Proportional Band

The proportional band is the range in pH from the setpoint value where the controller provides proportional control. For example, the desired setpoint for the process is pH 7.0 and the process requires that a reagent must be added to the process water to bring it up to pH 7.0. If the proportional band is set to pH 1.0, the controller will provide proportional output control over the range of pH 6.0 to 8.0. When the process is at pH 6.0, the controller will provide a 100% control output level (assuming that Phase is set to Direct). When the process is at pH 7.0, the proportional control will provide a 0% control output level. When the process is at pH 6.5 the proportional control will provide a 50% output. The output action is equal to the difference between the setpoint and the process value, divided by the proportional band value.

48

Image 48
Contents Digital PC sc and RC sc ¾-inch Combination pH/ORP Sensor Page Table of Contents Table of Contents Specifications Combination pH and ORP Sensor SpecificationsDigital Gateway Specifications Page Safety Information Precautionary LabelsGeneral Information Use of Hazard InformationGeneral Sensor Information General InformationSensor Body Styles Operating Precaution Digital GatewayPage Section Installation Wiring the sc Sensor to the Digital GatewayInstallation Proper Wire Preparation and InsertionWiring the Digital Gateway Cat. No Hard-wiring the Digital Gateway to the sc100 Wiring the Sensor at Terminal Block J5 Terminal Number Terminal Designation Wire ColorConnecting the Sensor to the sc1000 Connecting the Sensor using the Quick-connect FittingsDigital Gateway Dimensions Mounting the Digital GatewayPage Using the sc100 Controller Controller Key Functions/FeaturesUser Interface and Navigation Number Key FunctionUser Interface and Navigation Controller Display Features Important Key PressesDisplay Using the sc1000 Controller Display FeaturesUser Interface and Navigation Navigating the Menu Windows Main MenuKeypad List Box Message windowSensor Setup Sensor Diagnostics Menu for pH and ORPPH Sensor Setup Menu OperationConfigure OperationORP Sensor Setup Menu AC FrequencyPH Calibration One Point Automatic CalibrationTwo Point Automatic Calibration Operation One Point Manual Calibration Two Point Manual CalibrationORP Calibration Concurrent Calibration of Two Sensors for pH and ORPOne-point Manual Calibration Adjusting the Temperature Page Maintenance Maintenance ScheduleCleaning the Sensor MaintenanceTroubleshooting Error CodesTroubleshooting the pH or ORP Sensor Error CodesPage Replacement Parts and Accessories Replacement Items, Accessories, and Reagent and StandardsItem Description Catalog NumberPage How to Order Technical and Customer Service U.S.A. onlyA. Customers Information RequiredRepair Service CanadaLimited Warranty LimitationsLimitation of Remedies Page Product Safety Compliance InformationImmunity EmissionsFCC Part 15, Class a Limits Compliance InformationAppendix a Modbus Register Information Sensor Modbus RegistersGroup Name Tag Name Register Data Length Description Type Modbus Register Information Appendix B General pH Information PH Measurement TheoryWhere PID Controller Basics General pH InformationIntegral DerivativePage Index