Toshiba E6580772 instruction manual Setting of communication parameters

Page 12

E6580772

3.1.2 Setting of communication parameters

To enable F10M communication, set following parameters to the inverter. The parameters will be validated by rebooting a power supply or changing a reset setting (f899) to1.

When interrupting a transmission to change the setting of command input, reboot a power supply if necessary, since the data which have been received before the interruption of transmission are stored in the inverter.

cmod Operation command mode selection

(Set this parameter to 4 to carry out run/stop with F10M communication.)

fmod Speed setting mode selection

(Set this parameter to 9 to execute frequency command with F10M communication.)

f802 Inverter number

f830 Data type selection

f831 Input reference setting 1

f832 Input reference setting 2

f833 Input reference setting 3

f834 Input reference setting 4

f835 Input reference setting 5

f836 Input reference setting 6

f841 Monitor output setting 1

f842 Monitor output setting 2

f843 Monitor output setting 3

f844 Monitor output setting 4

f845 Monitor output setting 5

f846 Monitor output setting 6

f850 Communication error selection

f851 Communication error detecting time

f899 Reset function (1 to reset)

11

Image 12
Contents Optional add-on cassette E6580772③Safety Precautions „ Transportation and Installation„ Handling in general „ Wiring „ About operation„ About disposal of Inverter < Confirmation on accessories > Introduction< Type of F10M option unit > Contents Name and function of each section AppearanceE6580772③ Name of each section terminal TLF001Z<When the unit is installed alone> <When the unit is installed with another option>Connection to the inverter Connection to the inverter„ Connection with options E6580772③ Wiring „ PG interface TB2 terminalFunctional description F10M communication functionConnection of transmission cable Setting of communication parameters Communication parameters „ F10M communication parametersE6580772 ③ „ Other parameters PG input setting E6580772③ Vector control with sensorConnection of PG ↑V aInverter Selection of encoder type 100mVector control setting parameter Basic parametersExtended Parameter Speed loop ratio gain Speed loop integration gainSetting method for status monitoring Setting method for analog monitoringMonitoring method for feedback amount Accuracy of speed controlExternal diagram Specification Environment SpecificationPG feedback specification Specifications of transmission Warranty