Toshiba E6580772 instruction manual Specifications of transmission

Page 25

E6580772

<Specifications of transmission>

Use TOSLINE-F10M as a master station. For the connection with master station TOSLINE-F10 (standard type), refer to the instruction manual of “TOSLINE-F10M Communication function” (E6580773).

„Network (TOSLINE-F10M) specification

Item

Specification:TOSLINE-F10M (when repeater is used)

Number of transmission words

Max. 256W

Transmission distance

Max. 2Km

Valid transmission speed

100ms/256W

Number of connected station

Max. 256 stations (when 1W/1 unit)

„Inverter side TOSLINE-F10M specification

Item

Specification

Structure of transmission path

Party-line type

Signal transmission method

Start-stop synchronization

Access method

Poling & selecting method

Coding method

Base band, NRZ, Positive logic

Checking method

CRC check

Communication standard

Complies to EIA RS485.

Data signal speed

750kbps (high speed mode)

Number of transmission words

Max. 12W per one inverter (6W input, 6W output)

Processing time (note)

Max. 10ms (when only for scan transmission)

Communication service

Scan transmission, message transmission

Applicable model

Following functions of master station are possible.

 

z Function for selecting scan/message transmission

 

z Intermittent entering/secession function

 

z Function for selecting input data status at time of error

 

z MS monitoring function

(Note) Processing time means a cycle that the inverter gets access to the data and not including a transmission time, etc.

„Transmission cable specification

Item

 

Specification

 

Transmission

Shielded twisted pair cable

 

 

cable

 

 

 

Connecting

Connect SL1(L1), SL2(L2) and SG respectively.

 

method

Use twisted pair cable for SL1 and SL2.

 

 

(Note) Connect terminal resistors (both ends) to the end of the transmission path.

Transmission

Cable type

Cable length

Recommended manufacturer

cable length

CPEV-CU

500m or shorter

 

 

1.2mmφ (single core)

 

 

 

KMPEV-SB

400m or shorter

Showa Electric Wire & Cable

 

0.75mm2 (stranded wire)

 

Co., Ltd.

 

KMPEV-SB

200m or shorter

 

 

0.5mm2 (stranded wire)

 

 

Use same type of cable in one system.

24

Image 25
Contents E6580772③ Optional add-on cassette„ Transportation and Installation Safety Precautions„ Handling in general „ About operation „ Wiring„ About disposal of Inverter Introduction < Confirmation on accessories >< Type of F10M option unit > Contents Appearance Name and function of each sectionTLF001Z E6580772③ Name of each section terminal<When the unit is installed with another option> <When the unit is installed alone>Connection to the inverter Connection to the inverter„ Connection with options „ PG interface TB2 terminal E6580772③ WiringF10M communication function Functional descriptionConnection of transmission cable Setting of communication parameters „ F10M communication parameters Communication parametersE6580772 ③ „ Other parameters E6580772③ Vector control with sensor PG input setting↑V a Connection of PGInverter 100m Selection of encoder typeBasic parameters Vector control setting parameterExtended Parameter Speed loop integration gain Speed loop ratio gainSetting method for analog monitoring Setting method for status monitoringMonitoring method for feedback amount Accuracy of speed controlExternal diagram Environment Specification SpecificationPG feedback specification Specifications of transmission Warranty