E6580772③
Continuous operation depends on the status information that was before the communication error happens.
zDisplay of communication error will be [t].
zDisplay of trip will be [err8].
zWhen interrupting a transmission to change the setting of command input, reboot a power supply if necessary, since the data which have been received before the interruption of transmission are stored in the inverter.
zParameter setting of smaller communication number will be valid in case that the same setting values are allocated to the command input setting which are between 1 and 6, and also to the monitor output setting between 1 and 6.
(Note 3) The setting of communication error detection time is relating to the number of stations connected to the communication line. When changing the setting, fully consider the number of connected stations.
Other parameters
The following parameters reflect the transmitted data in the control of the inverter.
Parameter name | Title | Setting value | Details |
Operation | cmod | 4 | Validates the command sent from the F10M option. |
command mode |
|
| Operation such as run/stop from the other station will be |
selection |
|
| possible. |
Speed setting | fmod | 9 | Validates the speed reference value from the F10M option. |
mode selection |
|
|
|
Torque command | f420 | 9 | Validates the torque command value from the F10M option. |
selection |
|
|
|
Selection of | f422 | 5 | Validates the synchronized torque bias from the F10M |
synchronized |
|
| option. |
torque bias input |
|
|
|
Selection of | f423 | 5 | Validates the tension torque bias from the F10M option. |
tension torque |
|
|
|
bias input |
|
|
|
Load sharing gain | f424 | 5 | Validates the load sharing gain from the F10M option. |
input selection |
|
|
|
Power running | f440 | 5 | Validates power running torque limit from the F10M option. |
torque limit 1 |
|
|
|
selection |
|
|
|
Selection of | f442 | 5 | Validates regenerative torque limit from the F10M option. |
regenerative |
|
|
|
torque limit 1 |
|
|
|
14