Toshiba E6580772 instruction manual „ Other parameters

Page 15

E6580772

Continuous operation depends on the status information that was before the communication error happens.

zDisplay of communication error will be [t].

zDisplay of trip will be [err8].

zWhen interrupting a transmission to change the setting of command input, reboot a power supply if necessary, since the data which have been received before the interruption of transmission are stored in the inverter.

zParameter setting of smaller communication number will be valid in case that the same setting values are allocated to the command input setting which are between 1 and 6, and also to the monitor output setting between 1 and 6.

(Note 3) The setting of communication error detection time is relating to the number of stations connected to the communication line. When changing the setting, fully consider the number of connected stations.

„Other parameters

The following parameters reflect the transmitted data in the control of the inverter.

Parameter name

Title

Setting value

Details

Operation

cmod

4

Validates the command sent from the F10M option.

command mode

 

 

Operation such as run/stop from the other station will be

selection

 

 

possible.

Speed setting

fmod

9

Validates the speed reference value from the F10M option.

mode selection

 

 

 

Torque command

f420

9

Validates the torque command value from the F10M option.

selection

 

 

 

Selection of

f422

5

Validates the synchronized torque bias from the F10M

synchronized

 

 

option.

torque bias input

 

 

 

Selection of

f423

5

Validates the tension torque bias from the F10M option.

tension torque

 

 

 

bias input

 

 

 

Load sharing gain

f424

5

Validates the load sharing gain from the F10M option.

input selection

 

 

 

Power running

f440

5

Validates power running torque limit from the F10M option.

torque limit 1

 

 

 

selection

 

 

 

Selection of

f442

5

Validates regenerative torque limit from the F10M option.

regenerative

 

 

 

torque limit 1

 

 

 

14

Image 15
Contents E6580772③ Optional add-on cassetteSafety Precautions „ Transportation and Installation„ Handling in general „ Wiring „ About operation„ About disposal of Inverter < Confirmation on accessories > Introduction< Type of F10M option unit > Contents Appearance Name and function of each sectionTLF001Z E6580772③ Name of each section terminalConnection to the inverter <When the unit is installed alone><When the unit is installed with another option> Connection to the inverter„ Connection with options „ PG interface TB2 terminal E6580772③ WiringFunctional description F10M communication functionConnection of transmission cable Setting of communication parameters „ F10M communication parameters Communication parametersE6580772 ③ „ Other parameters E6580772③ Vector control with sensor PG input setting↑V a Connection of PGInverter 100m Selection of encoder typeVector control setting parameter Basic parametersExtended Parameter Speed loop integration gain Speed loop ratio gainAccuracy of speed control Setting method for status monitoringSetting method for analog monitoring Monitoring method for feedback amountExternal diagram Specification Environment SpecificationPG feedback specification Specifications of transmission Warranty