ADE-120ES (80 Kw Electric) Reversing, 3ø
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT: 208 VAC and 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTES: A. Fuse ratings are
B.Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct breaker size according to appliance amp draw rating and type of breaker used.
C.Circuit breakers for 3Ø dryers must be
OVEN SIZE | SERVICE |
| WIRE | APPROX. | MINIMUM | FUSING | CIRCUIT | ||
PHASE | AMP DRAW | Dual Element | |||||||
((Kw) | VOLTAGE | SERVICE | WIRE SIZE* | BREAKER | |||||
| 60 Hz | 50 Hz | Time Delay | ||||||
|
|
|
|
|
| ||||
80 | 208 | 3ø | 3 | 235 | 250 MCM | 300 | 300 | ||
80 | 240 | 3ø | 3 | 206 | 208 | 4/0 | 300 | 300 | |
80 | 380 | 3ø | 3 | 130 | 1 | 175 | 175 | ||
80 | 380 | 3ø | 4 | 130 | 1 | 175 | 175 | ||
80 | 416 | 3ø | 3 | 119 | 1 | 150 | 150 | ||
80 | 416 | 3ø | 4 | 119 | 1 | 150 | 150 | ||
80 | 480 | 3ø | 3 | 188 | 2 | 150 | 150 | ||
80 | 480 | 3ø | 4 | 108 | 2 | 150 | 150 | ||
80 | 575 | 3ø | 3/4 | 88 | 3 | 125 | 125 | ||
80 | 600 | 3ø | 3/4 | 85 | 3 | 125 | 125 |
*AWG Stranded Type Wire ... for individual lengths less than 100 feet. (Motor lead type wire is recommended)
IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is affixed to the back of the dryer, at the upper right hand corner. In the case of 208 VAC or 240 VAC, the supply voltage must match the electric service specifications of the data label exactly.
WARNING: 208 VAC and 240 Volts ARE NOT THE SAME. Any damage done to dryer components due to improper voltage connections will automatically VOID THE WARRANTY.
NOTE: ADC reserves the right to make changes in specifications at any time, without notice or obligation.