The main duct may be any shape or cross sectional area, so long as the minimum cross section area is provided. The illustrations on page 19 and page 20 show the minimum cross section area for multiple dryer round or square venting. These figures must be increased 10 square inches when rectangular main ducting is used, and the ratio of duct width to depth should not be greater than 3-1/2 to 1. These figures must be increased in proportion if the main duct run to the last dryer to where it exhausts to the outdoors is unusually long (over twenty [20] feet) or has numerous elbows (more than two [2]) in it. In calculating duct work size, the cross section area of a square or rectangular duct must be increased twenty (20) percent for each additional twenty

(20)feet. The diameter of a round exhaust must be increased ten (10) percent for each additional twenty (20) feet. Each 90° elbow is equivalent to an additional fifteen (15) feet.

IMPORTANT: For extended duct work runs, the cross section area of the duct work can only be increased to an extent. Maximum proportional duct work runs cannot exceed twenty (20) feet more than the original limitations of twenty (20) feet with two

(2)elbows. When the duct work approaches the maximum limits as noted in this manual, a professional HVAC firm should be consulted for proper venting information.

IMPORTANT: Exhaust back pressure measured by a manometer at each dryer exhaust duct area should not exceed 0.3 inches of water column.

The duct should be smooth inside with no projections from sheet metal screws or other obstructions which will collect lint. When adding ducts, the duct to be added should overlap the duct to which it is to be connected. ALL duct work joints must be taped to prevent moisture and lint from escaping into the building. Inspection doors should be installed at strategic points in the exhaust duct work for periodic inspection and clean-out of lint from the duct work.

NOTE: Where the exhaust passes through a wall, ceiling, or roof made of combustible materials, the opening must be 2-inches larger (all the way around) than the duct. The duct must be centered within this opening.

a.Outside Duck Work Protection

1)To protect the outside end of horizontal duct work from the weather, a 90° elbow bent downward should be installed where the exhaust exits the building. If the exhaust duct work travels vertically up through the roof, it should be protected from the weather by using a 180° turn to point the opening downward. In either case, allow at least twice the diameter of the duct between the duct opening and nearest obstruction.

IMPORTANT: DO NOT use screens, louvers, or caps on the outside of opening of exhaust duct work.

18

Image 22
Contents AD-120ES Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Section Important InformationSafety Precautions What to do if YOU Smell GASStandards Specifications / Component Identification SpecificationsADG-120ES ADE-120ES ADS-120ES Component Identification Dryer Front ViewDryer Rear View Installation Procedures Location RequirementsUNPACKING/SETTING UP Leveling Dryer Dryer Enclosure Requirements Fresh AIR Supply Exhaust Requirements General Exhaust Duct Work InformationPage Single Dryer Venting Multiple Dryer Common Venting Page ADG-120ES for GAS Models ADE-120ES for 80 KW Electric Models Page Electrical Information Electrical Service Specifications PER Dryer ADG-120ES Reversing, 3ø GAS ADS-120ES Reversing, 3ø SteamADE-120ES 72 Kw Electric Reversing, 3ø ADE-120ES 80 Kw Electric Reversing, 3ø Page Page GAS Information Gas SupplyType of Gas Page Page Steam Coil PH Level Installation InstructionsSteam Requirements , High Pressure Steam Damper System Steam Damper AIR System Connections Steam Damper System OperationSteam Damper AIR Piston Flow Control Operation Adjustment Preparation for Operation Preoperational Tests Natural GASPage Page Operating Instructions Shut Down Instructions Service SERVICE/PARTS InformationParts Warranty Warranty InformationReturning Warranty Cards Returning Warranty PartsPage Routine Maintenance CleaningDays Adjustments LubricationNo L.E.D. display microprocessor computer models only TroubleshootingDrive motor not operating does not start Blower motor not operating does not start Microprocessor computer display reads dSFL Microprocessor controller computer display reads doorPage No heat for Steam Models only No heat for Electric Models onlyDryer operates but is taking too long to dry Condensation on main door glassDryer or scraping noise at basket tumbler area Excessive noise and/or vibrationDrive motor only not operating does not start Failed reversing timer for Reversing Models onlyBlower impellor/fan motor only not operating does not start Heat unit not operating for only one 1 temperature selection Dryer operates but is taking too long to dry loadSail switch is fluttering for GAS and Electric Models only Failed hi-limit thermostat for GAS and Electric Models onlyDryer scraping noise at basket tumbler area Reversing Timer SPIN/DWELL Adjustments Timing LegendProcedure for Functional Check Replacement Components Microprocessor computer BoardDirect Spark Ignition DSI System