H. STEAM INFORMATION

It is your responsibility to have ALL steam plumbing connections made by a qualified professional to assure that the installation is adequate and conforms with local and state regulations or codes.

IMPORTANT: Failure to comply with the requirements stipulated in this manual can result in component failure which will VOID THE WARRANTY.

NOTE: The ADS-120ES is manufactured with a pneumatic (piston) damper system which requires an external supply of clean, dry, regulated air (80 psi +/- 10 psi). Refer to Steam Damper Air System Connections, Section H, item 3.

1.STEAM COIL PH LEVEL

The normal PH level for copper type steam coils must be maintained between a value of 8.5 to 9.5. For steel type steam coils the PH level must be maintained between a value of 9.5 to 10.5. These limits are set to limit the acid attack of the steam coils.

IMPORTANT: Coil failure due to improper PH level will VOID THE WARRANTY.

2.STEAM REQUIREMENTS , HIGH PRESSURE

a.Inlet ---- 1-1/4-inch supply line connection --- qty. one (1) at top manifold.

b.Return -- 1-1/4-inch return line connection --- qty. one (1) at bottom manifold.

Operating Steam Pressure

Maximum

125 psig

 

 

Minimum

100 psig

 

 

Heat Input (Normal Load)

13 Bhp

 

 

Consumption (Approximate)

450 lbs/hr

 

 

3.INSTALLATION INSTRUCTIONS

To insure that an adequate supply of steam is provided, be sure that the steam supply and steam return lines are sized and laid out as stipulated in this manual. Inadequate steam supply and steam return lines are sized and laid out as stipulated in this manual. Inadequate steam supply and steam return lines or improper steam plumbing will result in poor performance and can cause component failure. Clean, dry, regulated steam must be provided to the dryer.

IMPORTANT: Steam coil failure due to water hammer by wet steam will VOID THE WARRANTY.

31

Image 35
Contents AD-120ES Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Important Information SectionWhat to do if YOU Smell GAS Safety PrecautionsStandards Specifications Specifications / Component IdentificationADG-120ES ADE-120ES ADS-120ES Dryer Front View Component IdentificationDryer Rear View Location Requirements Installation ProceduresUNPACKING/SETTING UP Leveling Dryer Dryer Enclosure Requirements Fresh AIR Supply General Exhaust Duct Work Information Exhaust RequirementsPage Single Dryer Venting Multiple Dryer Common Venting Page ADG-120ES for GAS Models ADE-120ES for 80 KW Electric Models Page Electrical Information ADG-120ES Reversing, 3ø GAS ADS-120ES Reversing, 3ø Steam Electrical Service Specifications PER DryerADE-120ES 72 Kw Electric Reversing, 3ø ADE-120ES 80 Kw Electric Reversing, 3ø Page Page Gas Supply GAS InformationType of Gas Page Page Steam Requirements , High Pressure Installation InstructionsSteam Coil PH Level Steam Damper System Steam Damper System Operation Steam Damper AIR System ConnectionsSteam Damper AIR Piston Flow Control Operation Adjustment Preparation for Operation Natural GAS Preoperational TestsPage Page Operating Instructions Shut Down Instructions Parts SERVICE/PARTS InformationService Returning Warranty Parts Warranty InformationReturning Warranty Cards WarrantyPage Cleaning Routine MaintenanceDays Lubrication AdjustmentsDrive motor not operating does not start TroubleshootingNo L.E.D. display microprocessor computer models only Blower motor not operating does not start Microprocessor controller computer display reads door Microprocessor computer display reads dSFLPage No heat for Electric Models only No heat for Steam Models onlyCondensation on main door glass Dryer operates but is taking too long to dryExcessive noise and/or vibration Dryer or scraping noise at basket tumbler areaBlower impellor/fan motor only not operating does not start Failed reversing timer for Reversing Models onlyDrive motor only not operating does not start Dryer operates but is taking too long to dry load Heat unit not operating for only one 1 temperature selectionFailed hi-limit thermostat for GAS and Electric Models only Sail switch is fluttering for GAS and Electric Models onlyDryer scraping noise at basket tumbler area Timing Legend Reversing Timer SPIN/DWELL AdjustmentsMicroprocessor computer Board Procedure for Functional Check Replacement ComponentsDirect Spark Ignition DSI System