American Dryer ML-200 manual MLG-200 Gas Hp Blower/3 Hp Drive Motor

Page 22

2.Electrical Service Specifications

MLG-200 (Gas)

7.5 Hp Blower/3 Hp Drive Motor

ELECTRIC SERVICE SPECIFICATION (PER DRYER)

IMPORTANT: 208 VAC and 230 VAC ARE NOT THE SAME. When ordering, specify exact voltage.

NOTES: A. Fuse ratings are dual element-time delay-current limiting, class RK1 or RK5 ONLY.

B.Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct breaker size according to appliance amp draw rating and type of breaker used.

C.Circuit breakers for 3Ø dryers must be 3-pole type.

SERVICE

 

WIRE

APPROX.

MINIMUM

FUSING

CIRCUIT

PHASE

AMP DRAW

WIRE

Dual Element

VOLTAGE

SERVICE

BREAKER

 

60 Hz

50 Hz

SIZE*

Time Delay

 

 

 

 

 

 

 

 

 

 

 

 

208

3/4

37

---

4

60

80

 

 

 

 

 

 

 

 

230

3

36

---

4

60

80

 

 

 

 

 

 

 

 

380

3/4

---

20

8

30

40

 

 

 

 

 

 

 

 

416

3/4

---

19

8

30

40

 

 

 

 

 

 

 

 

460

3/4

18

---

8

30

40

 

 

 

 

 

 

 

 

* AWG Stranded Type Wire...for individual lengths less than 100 feet (30.48 meters).

WARNING: 208 VAC and 230 VAC ARE NOT THE SAME. Any damage done to dryer components due to improper voltage connections will automatically VOID THE WARRANTY.

IMPORTANT: The dryer must be connected to the electrical supply shown on the data label that

is affixed to the back of the dryer, at the upper right hand corner. In case of 208 VAC or 230 VAC, the supply voltage must match the electric service specifications of the data label exactly.

NOTE: ADC RESERVES THE RIGHT TO MAKE CHANGES IN SPECIFICATIONS AT ANY TIME, WITHOUT NOTICE or OBLIGATION.

18

Image 22
Contents ML-200 Non-Tilting Retain This Manual In a Safe Place For Future Reference Foryour Safety Page Table of Contents Section Procedure for Functional Check of Replacement Section Important InformationSafety Precautions What to do if YOU Smell GASPage Specifications GAS and Steam Models Component IdentificationML-200 Dimensions and Component Location Page Installation Procedures Reassembly of DryerPage Page Location Requirements Fresh AIR Supply Exhaust Requirements Page Compressed AIR Supply System Electrical Information Electrical RequirementsMLG-200 Gas Hp Blower/3 Hp Drive Motor MLS-200 Steam Hp Blower/3 Hp Drive Motor Page GAS Information Type of GAS Latest Edition Page Steam Information System Connections Section H, itemPage Compressed Air Supply Air Pressure Diagram Preparation for OPERATION/START-UP Preoperational Tests Basket Coating Shut Down Instructions Service SERVICE/PARTS InformationParts Warranty Warranty InformationReturning Warranty Cards Returning Warranty PartsPage Routine Maintenance CleaningSteam Dryers only Adjustments LubricationTUMBLER/BASKET Component System DescriptionsTumbler Basket Drive System AIR Blower Drive SystemSafety Devices Load Door SwitchesSteam Damper Actuator System Troubleshooting No DisplayFailed reversing contactor relay Failed microprocessor controller computer Page Blown 24 VAC control circuit fuse fuse Page For GAS Models only Excessive noise and/or vibration Tumbler basket out of alignment Procedure for Functional Check Replacement Components Page Page Manual Reset HI-LIMIT Instructions P O R T a N TADC113142 1- 04/21/00-8