H. STEAM INFORMATION

It is your responsibility to have ALL steam plumbing connections made by a qualified professional to assure that the installation is adequate and conforms with local and state regulations or codes.

IMPORTANT: Failure to comply with the requirements stipulated in this manual can result in component failure which will VOID THE WARRANTY.

NOTE: The IDS-170 is manufactured with a pneumatic (piston) damper system which requires an external supply of clean, dry, regulated air of 3.25 cfh (0.09 cmh) at 80 PSI +/- 10 PSI (5.51 bars +/- 0.68 bars). Refer to Steam Damper Air System Connections , Section H, item 4.

1.Steam Coil PH Level

The normal PH level for copper type steam coils must be maintained between a value of 8.5 to 9.5. For steel type steam coils the PH level must be maintained between a value of 9.5 to 10.5. These limits are set to limit the acid attack of the steam coils.

IMPORTANT: Coil failure due to improper PH level will VOID THE WARRANTY.

2.Steam Requirements - High Pressure

Inlet ---------

1-1/2" supply line connection ----

qty. one (1) at top manifold.

Return ------

1-1/2" return line connection -----

qty. one (1) at bottom manifold.

OPERATING STEAM PRESSURE

MAXIMUM

125 psig

 

862 kPa

 

 

 

 

MINIMUM

100 psig*

 

689 kPa

 

 

 

 

HEAT INPUT (NORMAL LOAD)

 

19 Bhp

 

 

 

 

CONSUMPTION (APPROXIMATE) @ 125 PSI

725 lbs/hr

 

329.1 kg/hr

 

 

 

 

Shaded areas are stated in metric equivalents

*Minimum operating pressure for optimum results.

3.Installation Instructions

To insure an adequate supply of steam is provided, be sure that the steam lines and steam return lines are sized and laid out as stipulated in this manual. Inadequate steam lines and steam return lines or improper steam plumbing will result in poor performance and can cause component failure. Clean, dry steam must be provided to the dryer.

IMPORTANT: Steam coil failure due to water hammer by wet steam will VOID THE WARRANTY.

a.The pressure of the condensate in the steam supply will cause water hammer and subsequent heat exchanger (steam coil) failure. The steam supply connection into the main supply line must be made with a minimum 10-inch (25.4 cm) riser. This will prevent any condensate from draining towards the dryer.

30

Image 34
Contents ID-170 Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Section Routine Maintenance Important Information Receiving and HandlingSafety Precautions What to do if YOU Smell GASStandards SPECIFICATIONS/COMPONENT Identification SpecificationsSpecifications Component Identification Page Installation Procedures Location RequirementsUNPACKING/SETTING UP Page Page Dryer Enclosure Requirements Fresh AIR Supply Requirements Exhaust Requirements Page Page Page Page Page Electrical Information Electrical RequirementsIDG-170 Gas IDS-170 Steam Page Page GAS Information Type of GAS Page Page Steam Information Operating Steam PressureSteam Damper System Compressed AIR Pressure Page Electric Service Exactly Preparation for OPERATION/START-UPPreoperational Tests Basket Coating Page Compressed AIR Requirements Compressed AIR Pressure AIR SupplyShut Down Instructions Service SERVICE/PARTS InformationParts Warranty Warranty InformationReturning Warranty Cards Returning Warranty PartsPage Routine Maintenance CleaningSteam Dryers Adjustments LubricationReversing Timer SPIN/DWELL Adjustments Timing LegendData Label Information Data LabelSerial Number Procedure for Functional Check Replacement Components P O RTA N T ADC 113331 1 08/27/01-25