American Dryer Corp MLS-460 manual Wiring Back the PLC Programmable Logic Controller

Page 65

3.0“DOOR Open” Problem

A “DOOR OPEN” message is generated by either the heater, the LOAD doors, or UNLOAD doors. The following information will address the LOAD doors and the UNLOAD doors signals, since they are associated with the tumbler (basket) junction box.

a.PROBABLE CAUSES;

1)WIRING BACK THE PLC (Programmable Logic Controller)

DS1-B=LOAD DOOR SWITCH DS2-B=UNLOAD DOOR SWITCH

b.POSSIBLE SOLUTIONS;

1)For quick check of LOAD and UNLOAD signals of the PLC perform the following:

Remove factory air from the dryer

With the Control Voltage “ON,” open the LOAD doors and locate the LOAD door switch actuator

Cycle the switch by hand and have someone watch PLC input indicator #6. It should go “ON” when the switch is down.

Open the UNLOAD doors and locate the UNLOAD doors switch actuator.

Cycle the switch by hand and have someone watch PLC (Programmable Logic Controller) input indicator #7. It should go “ON” when the switch is down. Do the associated L.E.D.’s (light emitting diode) come “ON” when switch is down?

If “YES,” wiring is okay

Check switch placement and door actuation

If “NO,” check associated:

Switch and wiring

Check wiring back to the tumbler (basket) junction box

Check wiring back to the rear controls

Check PLC (Programmable Logic Controller)

Refer to the blueprints: Main Electrical Panel Diagram

Tumbler (basket) junction box diagram

Rear panel controls wiring diagram

61

Image 65
Contents MLS-460 Installation/Operator’s Manual Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Motors ServicePower Malfunctions Important Information SectionExplosion could Result Safety PrecautionsPage Specifications SPECIFICATIONS/DIMENSIONSDimensions Reattach The Control Pendant Arm Installation ProceduresReassembly of Dryer Reassembly Instructions For Dryers Shipped In Three 3 Pieces Page Location Requirements Air Front Tilt Piston and Sprinkler Lines Internal AIR, ELECTRICAL, and Water ConnectionsPage Electric Tumbler Basket Motors Temperature Probe, Base, and Tumbler Basket DisconnectsPage Pendant Left Drum Motor Tumbler Basket Junction Box DisconnectExternal Supply Connections Condensate return line must be 1-1/4 pipe Exhaust Ducting Page Latest Edition Electrical RequirementsElectrical Requirements MLS-460 Steam Electrical Service SpecificationsPage Fresh AIR Supply Requirements Steam Requirements Steam InformationShut Down Instructions Preparation for Operation PRE START-UPCleaning Routine MaintenanceSuggested Cleaning Schedule Clean any lint accumulation from inside the heat consoleMonthly Tumbler Basket Support and Drive System Component System DescriptionsPage Page Main AIR Blower and Heat Reclaimer System Heat Reclaimer Adjustment Remove Electricity from the Unit Compressed AIR System Page Safety Devices Door Open Parts SERVICE/PARTS InformationService Returning Warranty Cards Warranty InformationWarranty Returning Warranty PartsPage Troubleshooting Table of Contents Number TroubleshootingMain Disconnect Will Not Turn On Power MalfunctionsVerify red Sprinkler Power on main panel to be illuminated If NO, refer to paragraph #1 above Sprinkler circuit may be defective Machine Main Power Shuts Down Blue Indicator OffSprinkler Circuit Components 3CR CRB Not UsedSprinkler Circuit Description Page Malfunctioning PLC Programmable Logic Controller Emergency Stop E-Stop Buttons 1, 2,Page General Description PLC Message HI-TEMP FaultPage Page Introduction Tumbler Basket Section Electrical MalfunctionsDrum Rotation Sensor PRS1 Rear Panel Control Problems Emergency Stop E-Stop Function If YES, refer to a If NO, refer to b PLC OUT PIN 1 = Drum Reverse PLC OUT PIN 2 = Drum Forward PLC OUT PIN 7 = Unload Door Open PLC OUT PIN 10 = Front UP DS1-B=LOAD Door Switch DS2-B=UNLOAD Door Switch Wiring Back the PLC Programmable Logic ControllerProbable Solutions Base Section Electrical Malfunctions Wiring Back to the PLC Programmable Logic Controller Lint Drawer Proximity SwitchesPage Probable Causes Load Level Unload Tumbler Reverse Tumbler Forward Pendant Control MalfunctionsSEL a = Load SEL B = Unload Tumbler Reverse Pendant --- PB2Tumbler Forward Pendant --- PB1 Wiring Back to PLC Programmable Logic Controller Fuse 4 on Main Electrical Panel Faulty SwitchesMLS-460 Pendant Assembly Diagram Wiring DiagramAnother Emergency Stop E-Stop Button Temperature SensingDisconnect Plug Faulty Switch Wiring Back to TB1 Exhaust RTD Resistive Temperature Device Sens1 Temperature Sensing Component DescriptionsWith the control voltage OFF Motors Circuit Wiring to the Analog Input ModuleVerify current setting Check circuit Check motor Retest LS-460 Idling LS-460 Running ADC113073 1- 01/14/00-15