3.Steam Supply and Condensate Return Connections

The steam supply into the dryer is made into the 2-1/2” F.T.P. pipe fitting located on top of the heat module console.

The maximum operating steam supply pressure is 125 psig (862 kPa).

The presence of condensate in the steam supply will cause water hammer and subsequent steam coil (battery) failure. The steam supply connection out of the main supply line must be made with a minimum 10-inch (25.4 cm) riser. This will reduce the amount of condensate in the steam supply.

Use flexible couplings at the supply and return connections. The dryer vibrates slightly when it runs and the piping connections may crack if they are hard piped to the dryer. Install shut-off valves in the supply and return lines.

An inverted bucket steam trap with an internal check valve is included with the dryer. The supply lines should be insulated. This will save energy and provide for the safety of the operator and maintenance personnel.

Water pockets in the supply line, caused by low points, will provide wet steam to the coil possibly causing steam coil damage. ALL horizontal runs of steam supply piping should be pitched 1/4-inch (0.08 cm) for the header. Install a bypass trap in any low point to eliminate wet steam.

The condensate return line must be 1-1/4” pipe.

19

Image 23
Contents MLS-460 Installation/Operator’s Manual Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Motors ServicePower Malfunctions Important Information SectionExplosion could Result Safety PrecautionsPage Specifications SPECIFICATIONS/DIMENSIONSDimensions Reattach The Control Pendant Arm Installation ProceduresReassembly of Dryer Reassembly Instructions For Dryers Shipped In Three 3 Pieces Page Location Requirements Air Front Tilt Piston and Sprinkler Lines Internal AIR, ELECTRICAL, and Water ConnectionsPage Electric Tumbler Basket Motors Temperature Probe, Base, and Tumbler Basket DisconnectsPage Pendant Left Drum Motor Tumbler Basket Junction Box DisconnectExternal Supply Connections Condensate return line must be 1-1/4 pipe Exhaust Ducting Page Latest Edition Electrical RequirementsElectrical Requirements MLS-460 Steam Electrical Service SpecificationsPage Fresh AIR Supply Requirements Steam Requirements Steam InformationShut Down Instructions Preparation for Operation PRE START-UPClean any lint accumulation from inside the heat console Routine MaintenanceCleaning Suggested Cleaning ScheduleMonthly Tumbler Basket Support and Drive System Component System DescriptionsPage Page Main AIR Blower and Heat Reclaimer System Heat Reclaimer Adjustment Remove Electricity from the Unit Compressed AIR System Page Safety Devices Door Open Parts SERVICE/PARTS InformationService Returning Warranty Parts Warranty InformationReturning Warranty Cards WarrantyPage Troubleshooting Table of Contents Number TroubleshootingMain Disconnect Will Not Turn On Power MalfunctionsVerify red Sprinkler Power on main panel to be illuminated If NO, refer to paragraph #1 above Sprinkler circuit may be defective Machine Main Power Shuts Down Blue Indicator OffSprinkler Circuit Components 3CR CRB Not UsedSprinkler Circuit Description Page Malfunctioning PLC Programmable Logic Controller Emergency Stop E-Stop Buttons 1, 2,Page General Description PLC Message HI-TEMP FaultPage Page Introduction Tumbler Basket Section Electrical MalfunctionsDrum Rotation Sensor PRS1 Rear Panel Control Problems Emergency Stop E-Stop Function If YES, refer to a If NO, refer to b PLC OUT PIN 1 = Drum Reverse PLC OUT PIN 2 = Drum Forward PLC OUT PIN 7 = Unload Door Open PLC OUT PIN 10 = Front UP DS1-B=LOAD Door Switch DS2-B=UNLOAD Door Switch Wiring Back the PLC Programmable Logic ControllerProbable Solutions Base Section Electrical Malfunctions Wiring Back to the PLC Programmable Logic Controller Lint Drawer Proximity SwitchesPage Probable Causes Tumbler Reverse Pendant --- PB2 Pendant Control MalfunctionsLoad Level Unload Tumbler Reverse Tumbler Forward SEL a = Load SEL B = UnloadTumbler Forward Pendant --- PB1 Wiring Diagram Fuse 4 on Main Electrical Panel Faulty SwitchesWiring Back to PLC Programmable Logic Controller MLS-460 Pendant Assembly DiagramAnother Emergency Stop E-Stop Button Temperature SensingDisconnect Plug Faulty Switch Wiring Back to TB1 Exhaust RTD Resistive Temperature Device Sens1 Temperature Sensing Component DescriptionsWith the control voltage OFF Motors Circuit Wiring to the Analog Input ModuleVerify current setting Check circuit Check motor Retest LS-460 Idling LS-460 Running ADC113073 1- 01/14/00-15