American Dryer Corp MLS-460 manual With the control voltage OFF

Page 76

3)Defective Analog Input Module For Channel

4)RTD (Resistive Temperature Device) Wiring To The “EXHAUST” 4 to 20 milliamphere (4 to 20 mA) Transmitter

5)Circuit Wiring To the Analog Input Module

b.POSSIBLE SOLUTIONS;

1)With the control voltage “OFF”

The exhaust RTD (Resistive Temperature Device) probe can be quickly checked, by locating its labeled disconnect in the right hand wire which is located on the main electrical enclosure panel.

Disconnect this plug and measure the resistance of the two (2) wires coming from the RTD; it should be in the 100 ohm (100 W) range.

If resistance is within range, wiring and RTD are okay

If the resistance is infinite (no measurements), or zero ohms (0 W), go directly to the intake RTD (Resistive Temperature Device) disconnect box and measure the RTD’s resistance directly

If the RTD resistance measurements is acceptable, check circuit wiring

If the RTD resistance measurements is not acceptable; replace RTD and retest

2)Defective 24 Volt DC Power Supply

With the control voltage “ON,” check that 100 volts AC is applied to the device’s AC input

If no voltage, check fuse #8 and wiring and retest Check that the device’s DC output indicator is “ON”

If “OFF,” this indicates that there is no 24 volts DC output

Disconnect the output voltage wires connected to the power supply and notice if the L.E.D. (light emitting diode) indicator responds

If the power supply responds to the disconnection, there is a problem with the driven LOAD and not the power supply itself

Check ALL loads and retest

Check that the device’s output voltage is 24 volts DC

If not, adjust it

3.DEFECTIVE ANALOG INPUT MODULE or CHANNEL Replace Analog Input Module

72

Image 76
Contents MLS-460 Installation/Operator’s Manual Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Power Malfunctions ServiceMotors Section Important InformationSafety Precautions Explosion could ResultPage SPECIFICATIONS/DIMENSIONS SpecificationsDimensions Reassembly of Dryer Installation ProceduresReattach The Control Pendant Arm Reassembly Instructions For Dryers Shipped In Three 3 Pieces Page Location Requirements Internal AIR, ELECTRICAL, and Water Connections Air Front Tilt Piston and Sprinkler LinesPage Temperature Probe, Base, and Tumbler Basket Disconnects Electric Tumbler Basket MotorsPage Pendant Tumbler Basket Junction Box Disconnect Left Drum MotorExternal Supply Connections Condensate return line must be 1-1/4 pipe Exhaust Ducting Page Electrical Requirements Electrical RequirementsLatest Edition Electrical Service Specifications MLS-460 SteamPage Fresh AIR Supply Requirements Steam Information Steam RequirementsShut Down Instructions PRE START-UP Preparation for OperationRoutine Maintenance CleaningSuggested Cleaning Schedule Clean any lint accumulation from inside the heat consoleMonthly Component System Descriptions Tumbler Basket Support and Drive SystemPage Page Main AIR Blower and Heat Reclaimer System Heat Reclaimer Adjustment Remove Electricity from the Unit Compressed AIR System Page Safety Devices Door Open Service SERVICE/PARTS InformationParts Warranty Information Returning Warranty CardsWarranty Returning Warranty PartsPage Troubleshooting Troubleshooting Table of Contents NumberVerify red Sprinkler Power on main panel to be illuminated Power MalfunctionsMain Disconnect Will Not Turn On If NO, refer to paragraph #1 above Machine Main Power Shuts Down Blue Indicator Off Sprinkler circuit may be defective3CR CRB Not Used Sprinkler Circuit ComponentsSprinkler Circuit Description Page Emergency Stop E-Stop Buttons 1, 2, Malfunctioning PLC Programmable Logic ControllerPage PLC Message HI-TEMP Fault General DescriptionPage Page Tumbler Basket Section Electrical Malfunctions IntroductionDrum Rotation Sensor PRS1 Rear Panel Control Problems Emergency Stop E-Stop Function If YES, refer to a If NO, refer to b PLC OUT PIN 1 = Drum Reverse PLC OUT PIN 2 = Drum Forward PLC OUT PIN 7 = Unload Door Open PLC OUT PIN 10 = Front UP Wiring Back the PLC Programmable Logic Controller DS1-B=LOAD Door Switch DS2-B=UNLOAD Door SwitchProbable Solutions Base Section Electrical Malfunctions Lint Drawer Proximity Switches Wiring Back to the PLC Programmable Logic ControllerPage Probable Causes Pendant Control Malfunctions Load Level Unload Tumbler Reverse Tumbler ForwardSEL a = Load SEL B = Unload Tumbler Reverse Pendant --- PB2Tumbler Forward Pendant --- PB1 Fuse 4 on Main Electrical Panel Faulty Switches Wiring Back to PLC Programmable Logic ControllerMLS-460 Pendant Assembly Diagram Wiring DiagramDisconnect Plug Faulty Switch Wiring Back to TB1 Temperature SensingAnother Emergency Stop E-Stop Button Temperature Sensing Component Descriptions Exhaust RTD Resistive Temperature Device Sens1With the control voltage OFF Circuit Wiring to the Analog Input Module MotorsVerify current setting Check circuit Check motor Retest LS-460 Idling LS-460 Running ADC113073 1- 01/14/00-15