IMPORTANT: A strain relief must be used where the input wiring enters the rear electric box.

Consistent gas pressure is essential at ALL gas connections. It is recommended that a 2-inch pipe gas loop be installed in the supply line serving a bank of dryers. An in-line pressure regulator must be installed in the gas supply line (header) if the (natural) gas pressure exceeds 12 inches of water column pressure.

NOTE: A water column test pressure of 3.5 inches for natural gas and 11 inches for L.P. (liquid propane) dryers is required at the gas valve pressure tap of each dryer for proper and safe operation.

A 1/8” N.P.T. plugged tap, accessible for a rest gauge connection, must be installed in the main gas supply line immediately upstream of each dryer.

IMPORTANT: Pipe joint compounds that resist the action of natural gas and L.P. gas must be used.

IMPORTANT: Test ALL connections for leaks by brushing on a soapy water solution (liquid detergent works well).

WARNING:NEVER TEST FOR LEAKS WITH A FLAME!!!

ALL components and materials must confirm to National Gas Code specifications. It is important that gas pressure regulators meet applicable pressure requirements and that gas meters be rated for the total amount of ALL the appliance BTU’s being supplied.

IMPORTANT: The dryer and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).

NOTE: The dryer must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure test of the gas supply system at test pressures equal to or less than 1/2 psig (3.5 kPa).

24

Image 28
Contents What do YOU do if YOU Smell GAS QUE Faire SI Vous Sentez UNE Odeur DE GAZFor Your Safety Pour Votre Sécurité Retain This Manual In a Safe Place For Future ReferenceFor Your Safety Page Table of Contents Section Routine Maintenance Section Important InformationSafety Precautions What to do if YOU Smell GASPage Section Specifications ML-79 WET Wash Component Identification Illus. No DescriptionInstallation Procedures Location RequirementsUnpacking and Setting UP Leveling DryerDryer Enclosure Requirements Make UP AIR Requirements Page Exhaust Requirements Page Page Be centered within this opening Electrical Information Electrical RequirementsElectrical Service Specifications GroundingElectrical Connections GAS Information Technical GAS DataS. Drill Material Size equivalent are as follows Page Page AIR Information Preparation for Operation and START-UP Preoperational Tests Gas DryersPreoperational Instructions Shut Down InstructionsService Service and Parts InformationParts Warranty Information Returning Warranty CardsPage Routine Maintenance CleaningDays Section Microprocessor Computer Models GAS Models Electric Models Low or inconsistent gas pressure Electric DryersPage Page Technical Information Data LabelProcedure for Functional Check Replacement Components Page Aquatex Humidity Sensor Instructions Figure #1ADC 07/29/99-25 12/08/00-10