2.ELECTRICAL SERVICE SPECIFICATIONS A. Gas and Steam Models
MLG-75 (Gas)
MLS-75 (Steam)
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT: 208 VAC and 230/240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTE: A. Fuse ratings are
B.Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct breaker size according to appliance amp draw rating and type of breaker used.
C.Circuit breakers for 3Ø dryers must be
SERVICE | PHASE | WIRE | APPROX. | MINIMUM | FUSING | CIRCUIT | ||
Dual Element | ||||||||
VOLTAGE | SERVICE | AMP DRAW | WIRE SIZE* | BREAKER | ||||
|
|
|
|
|
| Time Delay |
| |
120 | (60 Hz) | 1 | 2 | 13 | 10 | 20 | 25 | |
|
|
|
|
|
|
|
| |
208 | (60 Hz) | 1 | 2 | 8 | 14 | 12 | 15 | |
|
|
|
|
|
|
|
| |
208 | (60 Hz) | 3 | 3/4 | 5 | 14 | 8 | 15 | |
|
|
|
|
|
|
|
| |
240 | (50/60 Hz) | 3 | 3/4 | 5 | 14 | 8 | 15 | |
|
|
|
|
|
|
|
| |
240 | (50/60 Hz) | 1 | 2 | 7 | 14 | 12 | 15 | |
|
|
|
|
|
|
|
| |
(50 Hz) | 3 | 3/4 | 3 | 14 | 5 | 15 | ||
|
|
|
|
|
|
|
| |
416 | (50 Hz) | 3 | 3/4 | 3 | 14 | 5 | 15 | |
|
|
|
|
|
|
|
| |
460 | (60 Hz) | 3 | 3/4 | 3 | 14 | 5 | 15 | |
|
|
|
|
|
|
|
|
* AWG Stranded Wire ... for individual lenghts less than 100 feet.
IMPORTANT: Figures shown are for
IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is affixed to the back side of the upper/top control door. In the case of 208 VAC or 230/240 VAC, the supply voltage must match the electric service specifications of the data label exactly.
IMPORTANT: The wire size must be properly sized to handle the related current.
WARNING: 208 VAC and 230/240 VAC ARE NOT THE SAME. Any damage done to dryer components due to improper voltage connections will automatically VOID THE WARRANTY.
NOTE: ADC reserves the right to make changes in specifications at any time, without notice or obligation.
20