American Dryer Corp ML-130DR, ML-130 III Electrical Connections, Gas Model and Steam Model Dryers

Page 15

ELECTRIC

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT: 208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.

NOTES: A. When fuses are used they must be dual element, time delay, current limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse value, by applying either local and/or National Electrical Codes to listed appliance amp draw data.

B.Circuit breakers are thermal-magnetic (industrial) type ONLY. For others, calculate/verify correct breaker size according to appliance amp draw rating and type of breaker used.

C.Circuit breakers for 3-phase (3Ø) dryers must be 3-pole type.

SERVICE

 

WIRE

APPROX.

CIRCUIT

PHASE

AMP DRAW

VOLTAGE

SERVICE

BREAKER

 

 

 

60 Hz

50 Hz

 

 

 

72 kW

 

 

208

3

214

300

240

3

188

250

230

3

198

250

380

3

118

150

380

4*

118

150

400

4*

113

150

416

4*

108

150

460

3

98

125

480

3

94

125

575

3

78

100

 

 

75.6 kW

 

 

440

3

106

150

220

3

205

275

* 3-Wire is available.

 

 

 

7/31/08

IMPORTANT: The dryer must be connected to the electric supply shown on the data label. In the case of 208 VAC or 230/240 VAC, the supply voltage must match the electric service specifications of the data label exactly.

! WARNING

208 VAC and 230/240 VAC are not the same. Any damage done to dryer components due to improper voltage connections will automatically void the warranty.

NOTE: ADC reserves the right to make changes in specifications at any time without notice or obligation.

Electrical Connections

NOTE: A wiring diagram is included with each dryer and is located in the front control box area.

The only electrical input connections to the dryer are the 3-phase (3ø) power leads (L1, L2, and L3), GROUND, and in the case of 4-wire service, the neutral. Providing local codes permit, power connections to the dryer can be made by the use of a flexible underwriters laboratory listed cord/ pigtail (wire size must conform to rating of the dryer), or the dryer can be hard wired directly to the service breaker. In all cases, a strain relief must be used where the wire(s) enter the dryer electrical service (relay) box.

Gas Model and Steam Model Dryers

These electrical connections are made at the terminal block located in the electric service/relay box at the rear, upper left hand corner of the dryer. To gain access into this service box, the service cover (upper back guard) must be removed.

Electric Model Dryers

For electric model dryers made to operate at 208 VAC, or 230/240 VAC, the electrical input connection is made into the terminal block located at the upper rear of the dryer (refer to the illustration below). For electric model dryers made to operate at 380 VAC, 416 VAC, 440 VAC, or 480 VAC, the electrical input connection is made to the oven relay located at the upper rear of the dryer (refer to the illustration below). Input connection wiring must be sized properly to handle the dryer’s current draw. This information is printed on the dryer’s data label.

NOTE: A circuit servicing each dryer must be provided.

113335 - 12

www.amdry.com

15

Image 15
Contents American Dryer Corporation ML-130 III / ML-130DR Installation ManualDate of Purchase Model no RESELLER’S Name Serial Numbers Retain This Manual in a Safe Place for Future ReferenceTable of Contents Safety Precautions What To Do If You Smell GasPersonal injury or fire could result 113335 Electric ML-130 SpecificationsML-130 Specifications ML-130DR Specifications ML-130DR Specifications Leveling Dryer Installation ProceduresUnpacking/Setting Up Location RequirementsDryer Enclosure Requirements To Remove Top Console ModuleExhaust Transition Piece Gas and Electric Only Fresh Air Supply Requirements Exhaust RequirementsGeneral Exhaust Ductwork Information Multiple Dryer Common Venting Outside Ductwork ProtectionSingle Dryer Venting ML-130Electrical Requirements Electrical Service SpecificationsElectrical Information ML-130DR Multiple Dryer VentingElectrical Connections Gas Model and Steam Model DryersElectric Model Dryers Fire or explosion could result Gas InformationGrounding Gas SupplyML-130DR ML-130Steam Requirements, High Pressure Installation InstructionsSteam Information Steam Coil pH LevelSteam Damper System Operation Steam Damper Air System ConnectionsAir Requirements Compressed Air Supply Air Pressure Air ConnectionElectric Models Preparation for OperationPreoperational Test Heat Circuit Operational Test Gas ModelsOperating Instructions Shutdown InstructionsWarranty Information Service/Parts InformationRoutine Maintenance Reversing Timer Spin/Dwell Adjustments Data Label InformationLubrication Procedure for Functional Check Replacement Components Microprocessor Controller Computer BoardFor Models with DSI Module Type Fire Suppression System Manual Reset Burner Hi-Limit InstructionsTypical water supply Optional Manual Bypass ADC Part No 12 07/31/08