American Dryer Corp ML-130 III Manual Reset Burner Hi-Limit Instructions, Fire Suppression System

Page 26

Manual Reset

Burner Hi-Limit Instructions _________

Phase 7

This dryer was manufactured with a manual reset burner hi-limit thermostat, which is monitored by the Phase 7 computer. If the burner hi-limit is open prior to the start of the drying cycle, the dryer will start momentarily and then shut down, the Phase 7 computer will display “BURNER HIGH LIMIT FAULT” with an audio indication.

If the burner hi-limit opens during a drying cycle, the Phase 7 computer will also display the same error code described above, along with an audio indication. If the drum temperature is above 100° F (38° C), the dryer will continue to run with no heat for 3 minutes or until the drum temperature has dropped below 100° F (38° C). The clear/stop button on the Phase 7 keypad must be pressed to clear the error condition.

Dual Timer

This dryer was manufactured with a manual reset burner hi-limit thermostat. If the burner hi-limit is open prior to the start of the drying cycle, or during the cycle, the dryer will not recognize the open state of the burner hi-limit and will start or continue through the drying cycle with no heat. Manual reset hi-limit must be reset manually.

This hi-temperature condition may be caused due to a restricted exhaust, poor airflow, or improper burner operation.

The location of the burner hi-limit is on the right side of the burner box, looking at the burner from the front of the dryer.

! WARNING

Discontinue power to dryer before attempting to reset hi-limit.

Fire Suppression System _____________

Before You Start,

Check Local Codes and Permits

Call your local water company or the proper municipal authority for information regarding local codes.

IMPORTANT: It is your responsibility to have all plumbing connections made by a qualified professional to ensure that the plumbing installation is adequate and conforms to local, state, and federal regulations or codes.

It is the installer’s or owner’s responsibility to see that the necessary or required water, water pressure, pipe size, or connections are provided. The manufacturer assumes no responsibility if the F.S.S. is not connected, installed, or maintained properly.

Installation

Requirements

The connection point to the electric water solenoid valve is a 3/4-11.5 NH, the F.S.S. must be supplied with a minimum water pipe size of 1/2” and be provided with 40 psi +/- 20 psi (2.75 bar +/- 1.37 bar) of pressure. For use of optional manual bypass, a second source with the same piping and pressure requirements is required.

Flexible 1/2 feeds must be provided to avoid damage to electric water solenoid valve by vibration.

IMPORTANT: Flexible supply line/coupling must be used. Solenoid valve failure due to hard plumbing connections will void warranty.

If the rear area of the dryer, or the water supply is located in an area where it will be exposed to cold/freezing temperatures, provisions must be made to protect these water lines from freezing.

! WARNING

If the water in the supply line or water solenoid valve freezes, the F.S.S. will be inoperative!!

IMPORTANT: Appliance is to be connected to the water mains using a new hose set and the old hose set should not be reused.

Water Connection

The water connection is made to the 3/4-11.5 NH bushing located at the rear upper right area of the dryer. Flexible supply line/coupling must be used in effort to avoid damage to electric water solenoid valve.

IMPORTANT: Flexible supply line/coupling must be used. Solenoid valve failure due to hard plumbing connections will void warranty. It is recommended that a filter or strainer be installed in the water supply line.

26

American Dryer Corp.

113335 - 12

Image 26
Contents ML-130 III / ML-130DR Installation Manual American Dryer CorporationRetain This Manual in a Safe Place for Future Reference Date of Purchase Model no RESELLER’S Name Serial NumbersTable of Contents Personal injury or fire could result Safety PrecautionsWhat To Do If You Smell Gas 113335 ML-130 Specifications ElectricML-130 Specifications ML-130DR Specifications ML-130DR Specifications Location Requirements Installation ProceduresUnpacking/Setting Up Leveling DryerExhaust Transition Piece Gas and Electric Only Dryer Enclosure RequirementsTo Remove Top Console Module General Exhaust Ductwork Information Fresh Air Supply RequirementsExhaust Requirements ML-130 Outside Ductwork ProtectionSingle Dryer Venting Multiple Dryer Common VentingML-130DR Multiple Dryer Venting Electrical Service SpecificationsElectrical Information Electrical RequirementsElectric Model Dryers Electrical ConnectionsGas Model and Steam Model Dryers Gas Supply Gas InformationGrounding Fire or explosion could resultML-130 ML-130DRSteam Coil pH Level Installation InstructionsSteam Information Steam Requirements, High PressureAir Connection Steam Damper Air System ConnectionsAir Requirements Compressed Air Supply Air Pressure Steam Damper System OperationHeat Circuit Operational Test Gas Models Preparation for OperationPreoperational Test Electric ModelsShutdown Instructions Operating InstructionsService/Parts Information Warranty InformationRoutine Maintenance Lubrication Reversing Timer Spin/Dwell AdjustmentsData Label Information For Models with DSI Module Type Procedure for Functional Check Replacement ComponentsMicroprocessor Controller Computer Board Manual Reset Burner Hi-Limit Instructions Fire Suppression SystemTypical water supply Optional Manual Bypass ADC Part No 12 07/31/08