Sierra 830, 860, 840 instruction manual Maintenance

Page 47

Series 830/840/860 Instruction Manual

Chapter 4 Maintenance

 

 

the no-leak condition). Now, adjust this screw clockwise one quar- ter turn past this point, tighten the locknut and replace the cap. Apply power and test the controller for proper operation.

(Quick fix for oscillation). If your unit is experiencing oscillations at lower flows, apply power, apply the desired setpoint, and adjust the valve spring adjustment screw ¼ turn at a time clockwise (in- creasing the spring tension – see procedure above) during flow un- til the symptoms disappear. Adjust ¼ turn further and tighten the locknut.

If your unit is experiencing other symptoms listed above, you may require this more involved adjustment method. Obtain a voltmeter and prepare to monitor the voltage found on pins 4 to 6 on a D-connector, or D to F on a card-edge connector. Or, if these pins are inaccessible, turn off the power and remove the cable.

1.Remove the screws and/or nuts on the top of the controller electronics cover. Cut the yellow calibration sticker. Remove the silver zero and/or span plugs on the right side of the enclo- sure or turn the plastic access-hole doors to the vertical posi- tion. Pull the cover up and off. Re-connect the cable, apply gas pressure, and apply power to the controller. Connect a voltmeter to the two wires on the back PCA that are routed to the solenoid and set the scale for 30 volts or higher.

2.Determine if this controller has a 15-volt control circuit or a

30-volt control circuit. (Don’t confuse this with the setpoint or output signals – this is an internal voltage that energizes the valve coil to raise the valve seat and open the internal orifice). M and H instruments are ALWAYS 30-volt circuits, while L instruments can be either one, based mainly on their flow-rates. Units scaled for below 10 slpm are typically set up for 15 volts while those 10 slpm or over are set up for 30 vdc. (Note: this voltage is typically listed on the calibration certificate in the “Comment” section). If there is any question, contact the fac- tory for clarification.

3.Apply a 100% set point and monitor this valve voltage, allow- ing at least three minutes for stabilization. The voltage “win- dow” for a 100% setpoint is 13-18 volts for the 30-volt circuit and 9-11 volts for the 15-volt circuit. If the voltage is out of this specification, loosen the lock nut, and adjust the center ad- justment screw. Clockwise (downward) will increase the valve voltage, while counterclockwise will decrease it. Adjust

IM-83/84/86-H

4-13

Image 47 Contents
Table of Contents Customer Notice Table of Contents Table of Contents Troubleshooting List of Tables Table of Contents Introduction Using This ManualIntroduction Technical Assistance Safety InformationReceipt of System Components Flow Paths through the Transducer Series 800 Flow Sensing PrincipleSensor Temperature Distribution Installation Installation Overview VCO Fittings Installing the TransducerCompression Fittings NPT Fittings and 1/2-Inch Connections All Types VCR FittingsRecommended Wire Gauges Wiring the TransducerRecommended Wire Gauges Output Signal Connections Wiring Transducers with 20-Pin Card-Edge Connectors InputInput Signal Connections Controllers Only Depending on the valve voltage, connect as shown below Valve Purge and Valve Off Connections Controllers OnlyPin Connector Pin Designations Input Power Connections Wiring Transducers with 15-Pin D-ConnectorsInput Signal Connections Controllers Only 13. Valve Purge and Valve Off 15-Pin D-Connector 15 -Pin D-Connector Pin Assignments 16. Motor-Operated Rotary Valve Connector 10-Pin Connector Motor-Operated Valve Circular 10-Pin ConnectorMass Flow Meter Operation OperationElectromagnetic Valve Controllers Mass Flow Controller OperationMotor-Operated Rotary Valve Controllers Over-Range and Cold Sensor Lockout Circuit Mass Flow Controller FeaturesController Auto Shut-Off Feature Soft Start Response Times On-Off Control and Soft Start OptionPurging Reactive Gases Valve Purge FunctionPurging Non-Reactive Gases Operation Cleaning the Laminar Flow Element Flow Path MaintenanceLow Flow Transducers Low Flow Transducer LFE CleaningMedium Flow Transducers Medium Flow Transducer LFE CleaningHigh Flow Transducers High Flow Transducer LFE CleaningNPT-Type Transducers NPT Transducer LFE CleaningSensor Cleaning and Inspection Sensor MaintenanceSensor Electrical Test Electromagnetic Valves Low and Medium Flow Controllers Valve Maintenance Electromagnetic Valves High Flow Controllers Maintenance Motor-Operated Rotary Valves 840 L, M and H series Valve Adjustment Procedure Maintenance Maintenance Transducer Calibration Troubleshooting Flow Meters and Flow Controllers with Electromagnetic Valves Valve rotates continuously Flow Controllers with Motor-operated Rotary ValvesFactory Calibration-All Models Instructions for Returning Your Instrument for ServiceReturn Address Example 2 Finding the Actual Flow Rate Conversion of Flow Rate to Other T and P ConditionsExample 1 Changing Standard Conditions 14.7 460 + 10.00 = 3.47 lm 14.7 + Calculating For a Single Gas 880 Example Important Note about K-FACTORS Calculating Dual Gas MixturesNEO Gas Tables and K-factorsC2H6O CH 3SH Operating Specifications Appendix B Product SpecificationsVDC Physical Specifications Performance SpecificationsValve plug standard Neoprene, 4079 Kal-Rez Low Flow Body Transducer Mounting DimensionsMedium Flow Body High Flow Body Appendix B Specifications IM-83/84/86-H Flow Range, slpm NPT Flow Body100 200 Inlet Fnpt Appendix B Specifications