Rinnai 4500 installation manual LPG Cylinder Enclosure

Page 11

LPG Cylinder Enclosure

Enclosures for LP-gas supply cylinders shall be ventilated by openings at the level of the cylinder valve and at floor level. This shall be accomplished by one of the following:

A.One side of the enclosure shall be completely open; or

B.For an enclosure having four sides, a top and a bottom:

1.At least two ventilation openings at cylinder valve level shall be provided in the side wall, equally sized, spaced at 180 degrees, and unobstructed. Each opening shall have a total free area of not less than 1/2 square inch per pound (3.2 sq.cm/kg) of stored fuel capacity and not less than a total free area of 10 square inches (64.5 sq. cm).

2.Ventilation openings shall be provided at floor level and shall have a total free area of not less than 1/2 square inch per pound (3.2 s.cm/kg) of stored fuel capacity and not less than a total free area of 10 square inches (64.5 sq.cm). If ventilation openings at floor level are in a side wall, there shall be at least two openings. The bottom of the openings shall be at floor level and the upper edge no more than 5 inches (127 mm) above the floor. The openings shall be equally sized, spaced at 180 degrees and unobstructed.

3.Every opening shall have minimum dimensions so as to permit the entrance of a 1/8 inch (3.2 mm) diameter rod.

Cylinder valves shall be readily accessible for hand operation. A door on the enclosure to gain access to the cylinder valves is acceptable, provided it is non-locking and can be opened without the use of tools.

There shall be minimum clearance of 2 inches (50.8 mm) between the lower surface of the floor of the LP-gas supply cylinder enclosure and the ground.

Top openings at valve level

Minimum of 5” (12.7 cm) from floor to top of bottom opening

Minimum of 2” (5 cm) from floor bottom to ground level

Each opening shall have a total free area of not less than 1/2 square inch per pound (3.2 sq.cm/kg) of stored fuel capacity and not less than a total free area of 10 square inches (64.5 sq. cm).

Rinnai Corporation ROF4500

11

Image 11
Contents Rinnai Outdoor Fireplace Series Consumer Safety Information Table of ContentsSafety Behavior and Practices Safety Features Problem Cause Solution SpecificationsTroubleshooting With Fascia and Doors Dimensions DimensionsBody Assembly with Glass Doors Assembly SpecificationsBurner Assembly Body AssemblySample Installations Installation ApplicationsOperating the Appliance Operating InstructionsBefore Starting the Appliance Visual Inspection of Flame MaintenanceMaintenance Task Procedure Weather ProtectionItems included in carton ROF4500 ROF4501 ROF4502 Installation InstructionsBefore Installation General InstructionsLPG Cylinder Enclosure Definition of an Outdoor Area Description Clearance Required Additional Detail ClearancesPrepare Surround Installing Freestanding or Enclosed Masonry ApplicationsInstall Burner Assembly Install Burn Media and Complete Gas ConnectionMetal Lintel Prepare Framing DimensionsAttach Metal Lintel and Angled Clearance Brackets Timber stud Attach Mounting Brackets Install Doors if ApplicableInstall Body Assembly into Frame Install Steel FrameLayer 3 Single Layer of 14 Pieces of Large Quartz Installing Burn MediaLayer 1 Pumice Layer 2 Single Layer of Small QuartzLPG Cylinder Complete Gas ConnectionGuidelines for Cladding and Finishes QTY Parts ListPanel Burner Body Item No Quantity Description ROF4501 ROF4502 Item No Quantity Description Item No Quantity Description Outdoor Fireplace 4500 Fireplace Warranty InformationLimited Warranty Consumer SupportLimitation on warranties How do I get service? What is not covered?Rinnai Cheminée Extérieur Series Définitions de sécurité Instructions d’installationTable des matières Dispositifs de sécurité Comportements et pratiques de sécuritéDépannage Problème Raison SolutionLa vue est Au loin, 0.67 17 profondément Dimensions de brûleurDimensionsBody Dimensionsde corps Consoles darmature en acier Assemblée de brûleurAssemblée de corps Assemblée de corps avec les Portes en VerreAccessoires facultatifs Installations témoinOpérer lappareil Avant de commencer lappareilInspection visuelle de flame EntretienProtection contre les intempéries Articles inclus dans le carton ROF4500 ROF4501 ROF4502 Avant d’installationClôture de cylindre de LPG Définition dun secteur extérieur Description Espacements Information supplémentaire Requis EspacementsBordure plaquée Installation de lunité indépendante oumaçonnerie incluseInstallez le montage de brûleur Préparez la bordureLinteau en métal Préparez les dimensions de encadrementAttachez le linteau en métal et les équerres Ouvrez le Cabinet Dégrossi par DégrossiAttachez les supports Installez les portes si cest appropriéInstallez le montage de corps sur larmature Installez larmature en acierCouche 3 À une seule couche de 14 morceaux de grand quartz Installation des médias de brûlureCouche 1 Ponce Couche 2 À une seule couche du petit quartzCylindre-gas de propane liquide Accomplissez le raccordement de gazDirectives pour le revêtement et les finitions Quel est l’engagement de Rinnai ? Qu’est-ce qui est couvert ?Quelle est la durée de cette couverture ? Limitation des garanties implicites Rinnai Corporation ROF4500 Rinnai Corporation ROF4500 Rinnai’s other fine products