Napoleon Fireplaces B36DFP, B36DFN manual Vertical Termination

Page 12

12

VERTICAL TERMINATION

when (HT) < (VT)

Example 3:

Simple venting configurations

 

FIGURE 9

FIGURE10

 

V2

45°

See graph to determine the required vertical rise VT for the required horizontal run HT.

90° H2

V1

45°

H1 90°

90°

REQUIRED VERTICAL RISE IN FEET (VT)

V1

=5 ft

V2

=10 ft

VT

= V1 + V2 = 5 + 10 = 15 ft

H1

=3 ft

H2

=2.5 ft

HR

= H1 + H2 = 3 + 2.5 = 5.5 ft

HO

= .03(one 45º elbow + three 90º elbows - 135º)

 

= .03(45+90+90+90-135)=5.4

HT

=HR + HO = 5.5 + 5.4 = 10.9 ft

HT + VT = 10.9 + 15 = 25.9 ft

Formula 1:

HT < VT

 

 

10.9 < 15

Formula 2:

HT + VT < 40 feet

25.9 < 40

Since both formulas are met, this vent configuration is ac- ceptable.

HORIZONTAL VENT RUN

PLUS OFFSETS IN FEET (HT)

The shaded area within the lines represents acceptable values for HT and VT.

For vent configurations requiring more than one 45º and one 90° elbow , the following formulas apply:

Formula 1: HT < VT

Formula 2: HT + VT < 40 feet

W415-0484 / A / 07.26.06

Image 12
Contents W415-0484 / a What to do if YOU Smell GAS Table of Contents Conditions and Limitations General Instructions General InformationCare of GLASS, and Plated Parts Venting Venting LengthsAIR Terminal Locations Typical Vent Installations Special Vent InstallationsVenting Application Flow Chart Horizontal Termination VerticalWhen HT VT Horizontal TerminationDefinitions Elbow Vent Length ValuesWhen H T V T Simple venting configuration only one 45º and 90 elbowVertical Termination Formula 1 HT 3VT Formula 2 HT + VT 40 feet Example Installation Wall and Ceiling Protection Horizontal InstallationVertical Installation Using Flexible Vent Components Horizontal AIR Terminal InstallationGAS Installation Restricting Vertical VentsMobile Home Installation FramingConversion Kits Nailing TAB Installation Mantle InstallationDoor Removal & Installation L36 Louvre Installation FinishingLOG Placement Logo PlacementCharcoal Embers Glowing EmbersOptional Blower Installation Qualified StallerOptional FAN Installation GD36 Thermostatic Sensor ControlOperation / Maintenance MaintenanceOperating Instructions Not use any phone in your buildingAdjustments Pilot Burner AdjustmentVenturi Adjustment Replacements Common Replacement PartsCattena Utio Hchaud Trouble Shooting Guide Symptom Problem Test SolutionAfter Taking Pressure READINGS, be Sure to Turn Fireplace Service History W415-0484 / a