ADJUSTMENTS

PILOT BURNER ADJUSTMENT

Adjust the pilot screw to provide properly sized flame. Turn in a clockwise direction to reduce the gas flow.

Closing the air shutter will cause a more yellow flame, but can lead to carboning. Opening the air shutter will cause a more blue flame, but can cause flame lifting from the burner ports. The flame may not appear yellow immediately; allow 15 to 30 minutes for the final flame colour to be estab- lished.

FIGURE 47

FIGURE 48

VENTURI ADJUSTMENT

Air shutters have been factory set open according to the chart below:

AIR SHUTTER

NG

1/16"

LP

3/8"

These settings are for the maximum horizontal vent run.- Adjustment may be required depending on fuel type, vent configuration and altitude.

FIGURE 49

Air shutter adjustment must only be done by a

qualified installer!

FIGURE 50

VENTURI COVER

To access the air shutter, remove the two screws that se- cure the cover to the air housing, taking care not to dam- age the gasket.

W415-0484 / A / 07.26.06

Image 24
Contents W415-0484 / a What to do if YOU Smell GAS Table of Contents Conditions and Limitations General Instructions General InformationCare of GLASS, and Plated Parts Venting Venting LengthsAIR Terminal Locations Typical Vent Installations Special Vent InstallationsVenting Application Flow Chart Horizontal Termination VerticalWhen HT VT Horizontal TerminationDefinitions Elbow Vent Length ValuesWhen H T V T Simple venting configuration only one 45º and 90 elbowVertical Termination Formula 1 HT 3VT Formula 2 HT + VT 40 feet Example Installation Wall and Ceiling Protection Horizontal InstallationVertical Installation Using Flexible Vent Components Horizontal AIR Terminal InstallationGAS Installation Restricting Vertical VentsMobile Home Installation FramingConversion Kits Nailing TAB Installation Mantle InstallationDoor Removal & Installation L36 Louvre Installation FinishingLOG Placement Logo PlacementCharcoal Embers Glowing EmbersOptional Blower Installation Qualified StallerOptional FAN Installation GD36 Thermostatic Sensor ControlOperation / Maintenance MaintenanceOperating Instructions Not use any phone in your buildingAdjustments Pilot Burner AdjustmentVenturi Adjustment Replacements Common Replacement PartsCattena Utio Hchaud Trouble Shooting Guide Symptom Problem Test SolutionAfter Taking Pressure READINGS, be Sure to Turn Fireplace Service History W415-0484 / a