Napoleon Fireplaces B36DFN Using Flexible Vent Components, Horizontal AIR Terminal Installation

Page 15
HIGH TEMPERATURE SEALANT
INNER FLEX LINER
OUTER
FLEX
LINER FIGURE 21
FIGURE 19
INNER
SLEEVE
ROOF SUPPORT
FIGURE 20

15

USING FLEXIBLE VENT COMPONENTS

Use only approved aluminum flexible liner kits marked:

"Wolf Steel Approved Venting" as identified by the stamp only on the 8” outer liner.

HORIZONTAL AIR TERMINAL INSTALLATION

AVENT SHIELD MUST BE USED IF THE WALL TERMINAL IS INSTALLED ON COMBUSTIBLE, EXTERIOR SURFACES.

1.Cut or frame a hole in an exterior wall with a minimum oval or rectangle opening of 10½"w x 11 ½"h. Secure the firestop spacer over the opening to the interior wall, ensur- ing 2" clearance above the vent pipe opening.

2.Stretch the 5" diameter aluminum flexible liner to the required length taking into account the additional length needed for the finished wall surface. Slip the liner a mini- mum of 2" over the inner sleeve of the air terminal and secure with 3 #8 screws. Apply a heavy bead of the high temperature sealant.

3.Using the 8" diameter flexible aluminum liner, slide over the outer combustion air sleeve of the air terminal and secure with 3 #8 screws. Seal as before.

FIGURE 18

For safe and proper operation of the fireplace, follow the vent- ing instructions exactly.

All inner exhaust and outer intake vent pipe joints may be sealed using either Red RTV high temp silicone sealant or Black high temp Mill Pac with the exception of the fireplace exhaust flue collar which must be sealed using Mill Pac (not supplied).

5.Apply a heavy bead of the high temperature sealant, Mill Pac, to the inside of the 5" liner approximately 1" from the end. Slip the liner a minimum of 2" over the fireplace vent collar and secure with 3 #8 screws.

6.Using the 8" diameter flexible aluminium liner, apply sealant, slide a minimum of 2" over the fireplace combus- tion air collar and secure with 3 #8 screws.

7.If more liner needs to be used to reach the fireplace, couple them together as illustrated. The vent system must be supported approximately every 3 feet for both vertical and horizontal runs. Use noncombustible strapping to maintain the minimum 1" clearance to combustibles.

VERTICAL AIR TERMINAL INSTALLATION

1. Fasten the roof support to the roof using the screws provided. The roof support is optional.

In this case the venting is to be a d e q u a t e l y

supported using either an alternate method suitable to

the authority having jurisdiction or the optional roof support.

The air terminal mounting plate may be recessed into the exterior wall or siding by 1½", the depth of the return flange.

2.Stretch the exhaust to the required length. Slip the liner a minimum of 2" over the inner sleeve of the air terminal and secure with 3 #8 screws. Seal using a heavy bead of the high temperature sealant.

3.Repeat using air intake vent pipe.

AIR

TERMINAL

CONNECTOR

4.Insert the liners through the firestop maintaining the required clearance to combustibles. Holding the air termi- nal (lettering in an upright, readable position), secure to the exterior wall and make weather tight by sealing with caulking (not supplied).

4. Thread the air terminal pipe assembly down through the roof. The air terminal must be located vertically and

plumb. Attach the air terminal assembly to the

roof support, ensuring that a minimum 16" of air terminal will penetrate the roof when fastened.

DO NOT CLAMP THE FLEXIBLE ALUMINIUM LINER.

W415-0484 / A / 07.23.06

Image 15
Contents W415-0484 / a What to do if YOU Smell GAS Table of Contents Conditions and Limitations General Instructions General InformationCare of GLASS, and Plated Parts Venting Lengths VentingAIR Terminal Locations Special Vent Installations Typical Vent InstallationsHorizontal Termination Vertical Venting Application Flow ChartElbow Vent Length Values When HT VTHorizontal Termination DefinitionsSimple venting configuration only one 45º and 90 elbow When H T V TVertical Termination Formula 1 HT 3VT Formula 2 HT + VT 40 feet Example Installation Wall and Ceiling Protection Horizontal InstallationVertical Installation Horizontal AIR Terminal Installation Using Flexible Vent ComponentsRestricting Vertical Vents GAS InstallationMobile Home Installation FramingConversion Kits Mantle Installation Nailing TAB InstallationFinishing Door Removal & Installation L36 Louvre InstallationGlowing Embers LOG PlacementLogo Placement Charcoal EmbersQualified Staller Optional Blower InstallationGD36 Thermostatic Sensor Control Optional FAN InstallationNot use any phone in your building Operation / MaintenanceMaintenance Operating InstructionsAdjustments Pilot Burner AdjustmentVenturi Adjustment Common Replacement Parts ReplacementsCattena Utio Hchaud Symptom Problem Test Solution Trouble Shooting GuideAfter Taking Pressure READINGS, be Sure to Turn Fireplace Service History W415-0484 / a