23 | TROUBLESHOOTING |
Manual Ignition System (Cont.) |
TROUBLESHOOTING
Manual Ignition System (Continued)
WARNING: If you smell gas
•Shut off gas supply.
•Do not try to light any appliance.
•Do not touch any electrical switch; do not use any phone in your building.
•Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions
•If you cannot reach your gas supplier, call the fire department.
OBSERVED PROBLEM | POSSIBLE CAUSE | REMEDY | ||
Fireplace produces unwanted odors | 1. | Gas leak. See Warning statement | 1. | Locate and correct all leaks (see Check- |
|
| above |
| ing Gas Connections, page 13) |
|
|
|
|
|
Fireplace shuts off in use | 1. | High or gusting winds | 1. | Fireplace has been tested for up to |
|
|
|
| 40 mph winds. However, extreme con- |
|
|
|
| ditions may occur. See Lighting Instruc- |
|
|
|
| tions on page 16 |
| 2. | Low line pressure | 2. | Check local propane/LP or natural gas |
Burner backfiring during combustion |
|
|
| company |
| 3. | Pilot is partially clogged | 3. | Clean pilot (see Cleaning and Mainte- |
|
|
|
| nance, page 20 |
| 4. | Improper or restricted venting. | 4. | Locate and correct all vent conditions |
|
|
|
| (seeCheckingforProperVenting,page8) |
| 5. | Clogged burner tube, blocked orifice | 5. | Clean burner tube and orifice, adjust air |
|
| or improper burner air adjustment. |
| shutter.(seeInspectingBurners,page19) |
| 6. | Bad thermopile or thermocouple | 6. | Replace faulty components |
| 7. | Vent cap improperly installed or blocked | 7. | Check for proper installation or remove |
|
|
|
| debris or blockage. |
|
|
|
|
|
Gas odor even when control knob is in OFF | 1. | Gas leak. See Warning statement | 1. | Locate and correct all leaks (see Check- |
position |
| above |
| ing Gas Connections, page 13) |
|
|
|
|
|
Gas odor during combustion | 1. | Gas leak. See Warning statement | 1. | Locate and correct all leaks (see Check- |
|
| above |
| ing Gas Connections, page 13) |
|
|
|
|
|
Dark residue on logs or inside of fireplace | 1. | Improper log placement | 1. | Properly locate logs (see Installing Logs, |
|
|
|
| Lava Rock, and Glowing Embers, page 15) |
| 2. | Air holes at burner inlet blocked | 2. | Clean out air holes at burner inlets, Pe- |
|
|
|
| riodically repeat as needed |
| 3. | Burner flame holes blocked | 3. | Remove blockage or replace burner |
| 4. | Improper venting or excessive blockage | 4. | Have the vent system inspected, includ- |
|
|
|
| ing the termination cap. Remove any |
|
|
|
| restrictions or blackage |
| 5. | Excessive amounts of embers and pan | 5. | Clearexcessembersfromaroundtherear |
|
| material |
| main ports. Use a minimum of one layer |
|
|
|
| of smaller ember peices to acheive the |
|
|
|
| best glowing effect over the visible areas |