18
INSTALLATION
Optional Wireless
INSTALLATION
Continued
Installing
1.Remove battery cover on back of remote control unit.
2.Attach terminal wires to the battery (not included). Place battery into the battery housing.
3.Replace battery cover onto remote control unit.
Terminal Wires | Battery Cover |
Remote Control | |
Battery | Unit |
Battery
Housing
Figure 37 - Installing Battery in Hand-Held Remote Control Unit
GAS LINE HOOK-UP
WARNING: Before you proceed, make sure your gas supply is OFF.
WARNING: Gas line hookup should be done by your gas supplier or a qualified service person.
An equipment shutoff valve has been included in the appliance’s gas supply system. You may consider installing an extra gas shutoff valve outside the appliance’s enclosure (check with local codes) where it can be accessed more conveniently with a key through a wall as shown in Figure 38.
Route a 1/2" NPT black iron gas line towards the appliance coming in from the left. It is recommended to route the pipe between the stand of the firebox and the surround of the fireplace (see Figure 39).
IMPORTANT: The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig. (3.5 kPa). The appliance must be isolated from the gas supply piping system by closing its individual equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig. (3.5 kPa).
CAUTION: Do not kink flexible gas line.
CAUTION: Compounds used on threaded joints of gas piping shall be resistant to the action of Liquefied Petroleum (LP or propane), and should be applied lightly to ensure excess sealant does not enter the gas line.
1.Install a sediment trap between the incoming gas line and the gas control valve (see Figure 39). The sediment trap should extend down the center of the pipe. Refer to your local codes.
2.Prepare incoming gas line and check with local codes regard- ing the use of teflon tape. Complete your gas line installation by connecting incoming gas line with flexible gas line. Se- cure tightly with a wrench, but Do NOT Overtighten.
WARNING: All gas piping and connections must be tested for leaks after the installation is completed.
After ensuring that the gas valve is open, apply a soap and water solution to all connections and joints. If bubbles appear, leaks can be detected and corrected.
Do not use an open flame for leak testing and do not operate any appliance if a leak is detected.
Shutoff Valve
Key
Extension
Figure 38 - Typical Exterior Wall Gas Shutoff Installation
Incoming 1/2"
Gas Line
Permitted by
Local Codes
| Wall |
| Appliance |
Back | |
Of |
|
Sediment Trap (Not Supplied)
Figure 39 - Sediment Trap