Desa VSGF33PRC, VSGF33NRC installation manual Vent Pointing Down, Propane/LP

Page 13

Installation

Continued

For propane/LP units, the installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11" and 14" of water. If you do not reduce incoming gas pres- sure, heater regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 17. Pointing the vent down protects it from freezing rain or sleet.

CAUTION:Useonlynew,black ironorsteelpipe.Internally-tinned copper tubing may be used in cer- tainareas.Checkyourlocalcodes. Usepipeof1/2"diameterorgreater to allow proper gas volume to fire- place. If pipe is too small, undue loss of volume will occur.

Installation must include an equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from fireplace (see Figure 18).

IMPORTANT: Install equipment shutoff valve in an accessible location. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.

Check your building codes for any special re- quirements for locating equipment shutoff valve to fireplaces.

Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged fire- place valves. Never use sealant on flare threads.

External

Propane/LP

Regulator

Supply Tank

Vent Pointing Down

Figure 17 - External Regulator on Propane/LP Supply Tank with Vent Pointing Down

WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.

We recommend that you install a sediment trap in supply line as shown in Figure 18. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and fireplace. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into fireplace gas controls. If sediment trap is not installed or is installed wrong, fireplace may not run properly.

CSA Design-Certified

Equipment Shutoff Valve

With 1/8" NPT Tap*

 

Natural Gas

 

From Gas

 

Meter

 

(5" W.C.** to

 

10.5" W.C.

3" Minimum

Pressure)

 

 

 

 

 

Propane/LP

Cap Pipe

Tee

 

From External

Nipple

Joint

 

Regulator

 

 

 

 

(11" W.C.**

 

 

 

 

Sediment Trap

 

to 14" W.C.

 

 

 

 

Pressure)

Figure 18 - Gas Connection

*Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See

Accessories, page 32.

** Minimum inlet pressure for purpose of input adjustment.

119304-01A

www.desatech.com

13

Image 13
Contents Remote-ready fireplace System VSGF33PRC and VSGF33NRCTable of Contents Safety Information Local Codes Product IdentificationAccessory Product FeaturesUnpacking Air For Combustion VentilationProviding Adequate Ventilation AIR for Combustion VentilationDetermining FRESH-AIR Flow for Fireplace Location Ventilation Air From Inside Building Ventilation AIRVentilation Air From Outdoors Installing Hood InstallationCheck GAS Type Electrical HookupExample Installation ClearancesInstalling Gas Piping to Fireplace Location, Conventional Fireplace InstallationActual Framing Height Built-In Fireplace InstallationFront Width DepthMantel Clearances for Built-In Installation Installing Gas Piping to Fireplace LocationInstallation Items Needed Propane/LP Vent Pointing DownChecking GAS Connections Connecting Fireplace to Gas SupplyNatural Gas Test Pressures Equal To or Less Than Psig 3.5 kPa Pressure Testing Fireplace Gas ConnectionsInstalling Bottom Logs Installing LogsOperating Fireplace For Your Safety Read Before LightingLighting InstructionsTo Turn OFF GAS To Appliance Manual Lighting ProcedureOpTIONAL Hand-Held Remote OperationThermostat Model HRC200 On/Off Model HRC100Optional Blower Operation Inspecting BurnersPilot Flame Pattern Main burnerInspecting Burners Cleaning MaintenanceBurner Injector Holder and Pilot Air Inlet Hole Wiring Diagram Cleaning MaintenanceSpecifications LogsObserved Problem Possible Cause Remedy TroubleshootingDiagram, TroubleshootingStalling Logs, Statement above Gas leak. See WarningService Hints Replacement PartsTechnical Service Parts Under WarrantyIllustrated Parts Breakdown Log Base Assembly Models VSGF33NRC and VSGF33PRCParts List Fireplace mOdels VSGF33NRC and VSGF33PRC Illustrated Parts BreakdownParts List Receiver and HAND-HELD Thermostat Remote Control KIT HRC200 AccessoriesReceiver and HAND-HELD Remote Control KIT HRC100 Equipment Shutoff Valve GA5010WALL-MOUNT ON/OFF Switch AccessoriesWALL-MOUNT Thermostat 119304-01A 119304-01A Keep this Warranty Warranty InformationLimited Warranty VENT-FREE GAS Fireplace