Desa VSGF33PRC, VSGF33NRC installation manual Ventilation AIR, Ventilation Air From Inside Building

Page 7

AIR FOR COMBUSTION

AND VENTILATION

Continued

Example:

 

40,000

 

Gas water heater

 

Btu/Hr

Vent-free fireplace

+

33,000

Btu/Hr

Total

=

73,000

Btu/Hr

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

__________ Btu/Hr (maximum the space can support)

__________ Btu/Hr (actual amount of Btu/Hr used) Example: 51,200 Btu/Hr (maximum the space

can support)

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un- confined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 3). You can also remove door into adjoining room (see option 3, Figure 3). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

73,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide ad- ditional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoin-

ing room. If the extra space provides an unconfined

Ventilation

 

Grills

 

Into Adjoining

Or

Room,

Remove

Option 1

Door into

 

 

Adjoining

 

Room,

 

Option

 

3

12"

Ventilation Grills

Into Adjoining Room,

Option 2

space, remove door to adjoining room or add

ventilation grills between rooms. See Ventilation

Air From Inside Building.

B. Vent room directly to the outdoors. See Ventila-

tion Air From Outdoors.

C. Install a lower Btu/Hr fireplace, if lower Btu/Hr

size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an un- confined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be oper- ated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA54 Section 5.3 or applicable local codes.

12"

Figure 3 - Ventilation Air from Inside

Building

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat- controlled power vent. Heated air entering the attic will activate the power vent.

 

Outlet

Ventilated

 

Attic

 

Air

 

 

Outlet

 

 

Air

 

To Attic

 

 

 

 

To

 

 

Crawl

Inlet

 

Space

 

 

Air

 

 

 

Inlet Air

Ventilated

 

Crawl Space

 

 

Figure 4 - Ventilation Air from Outdoors

119304-01Awww.desatech.com

Image 7
Contents Remote-ready fireplace System VSGF33PRC and VSGF33NRCTable of Contents Safety Information Local Codes Product IdentificationAir For Combustion Ventilation Product FeaturesAccessory UnpackingProviding Adequate Ventilation AIR for Combustion VentilationDetermining FRESH-AIR Flow for Fireplace Location Ventilation Air From Inside Building Ventilation AIRVentilation Air From Outdoors Electrical Hookup InstallationInstalling Hood Check GAS TypeExample Installation ClearancesInstalling Gas Piping to Fireplace Location, Conventional Fireplace InstallationDepth Built-In Fireplace InstallationActual Framing Height Front WidthMantel Clearances for Built-In Installation Installing Gas Piping to Fireplace LocationInstallation Items Needed Propane/LP Vent Pointing DownChecking GAS Connections Connecting Fireplace to Gas SupplyNatural Gas Test Pressures Equal To or Less Than Psig 3.5 kPa Pressure Testing Fireplace Gas ConnectionsInstalling Bottom Logs Installing LogsInstructions For Your Safety Read Before LightingOperating Fireplace LightingRemote Operation Manual Lighting ProcedureTo Turn OFF GAS To Appliance OpTIONAL Hand-HeldThermostat Model HRC200 On/Off Model HRC100Main burner Inspecting BurnersOptional Blower Operation Pilot Flame PatternInspecting Burners Cleaning MaintenanceBurner Injector Holder and Pilot Air Inlet Hole Logs Cleaning MaintenanceWiring Diagram SpecificationsObserved Problem Possible Cause Remedy TroubleshootingDiagram, TroubleshootingStalling Logs, Statement above Gas leak. See WarningParts Under Warranty Replacement PartsService Hints Technical ServiceIllustrated Parts Breakdown Log Base Assembly Models VSGF33NRC and VSGF33PRCParts List Fireplace mOdels VSGF33NRC and VSGF33PRC Illustrated Parts BreakdownParts List Equipment Shutoff Valve GA5010 AccessoriesReceiver and HAND-HELD Thermostat Remote Control KIT HRC200 Receiver and HAND-HELD Remote Control KIT HRC100WALL-MOUNT ON/OFF Switch AccessoriesWALL-MOUNT Thermostat 119304-01A 119304-01A Keep this Warranty Warranty InformationLimited Warranty VENT-FREE GAS Fireplace