Desa VSGF33PRC, VSGF33NRC installation manual Test Pressures Equal To or Less Than Psig 3.5 kPa

Page 15

Installation

Continued

CAUTION: Make sure exter- nal regulator has been installed between propane/LPsupply and fireplace. See guidelines under Connecting Fireplace to Gas Supply, page 14.

Pressure Testing Gas Supply

Piping System

Test Pressures In Excess Of 1/2 PSIG

(3.5 kPa)

1. Disconnect fireplace with its main gas valve (control valve) and equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig will damage fireplace regulator.

2. Cap off open end of gas pipe where equipment shutoff valve was connected.

3. Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas, or using compressed air.

4. Check all joints of gas supply piping system. Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.

5. Correct all leaks at once.

6. Reconnect fireplace and equipment shutoff valve to gas supply. Check reconnected fittings for leaks.

Test Pressures Equal To or Less Than

1/2 PSIG (3.5 kPa)

1. Close equipment shutoff valve (see Figure 21).

2. Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas, or using compressed air.

3. Check all joints from gas meter to equipment shutoff valve for natural gas or propane/LP sup- ply to equipment shutoff valve for propane/LP (see Figures 22 and 23). Apply noncorrosive leak detection fluid to all joints. Bubbles form- ing show a leak.

4. Correct all leaks at once.

Open

Equipment

Shutoff

Valve

Closed

Figure 21 - Equipment Shutoff Valve

Equipment Shutoff Valve

Gas Meter

Gas Control Valve

Figure 22 - Checking Gas Joints for

Natural Gas

Equipment Shutoff Valve

Propane/LP

Supply Tank

Gas Control Valve

Figure 23 - Checking Gas Joints for

Propane/LP Gas

Pressure Testing Fireplace Gas

Connections

1. Open equipment shutoff valve (see Figure 21).

2. Open main gas valve located on or near gas meter for natural gas or open propane/LP supply tank valve.

3. Make sure control knob of fireplace is in the OFF position.

4. Check all joints from equipment shutoff valve to gas control valve (see Figures 22 or 23). Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.

5. Correct all leaks at once.

6. Light fireplace (see Operating Fireplace, page

17. Check all other internal joints for leaks.

7. Turn off fireplace (see To Turn Off Gas to Appliance, page 18).

119304-01A

www.desatech.com

15

Image 15
Contents Remote-ready fireplace System VSGF33PRC and VSGF33NRCTable of Contents Safety Information Local Codes Product IdentificationAir For Combustion Ventilation Product FeaturesAccessory UnpackingAIR for Combustion Ventilation Providing Adequate VentilationDetermining FRESH-AIR Flow for Fireplace Location Ventilation AIR Ventilation Air From Inside BuildingVentilation Air From Outdoors Electrical Hookup InstallationInstalling Hood Check GAS TypeExample Installation ClearancesInstalling Gas Piping to Fireplace Location, Conventional Fireplace InstallationDepth Built-In Fireplace InstallationActual Framing Height Front WidthInstalling Gas Piping to Fireplace Location Mantel Clearances for Built-In InstallationInstallation Items Needed Propane/LP Vent Pointing DownConnecting Fireplace to Gas Supply Checking GAS ConnectionsNatural Gas Test Pressures Equal To or Less Than Psig 3.5 kPa Pressure Testing Fireplace Gas ConnectionsInstalling Bottom Logs Installing LogsInstructions For Your Safety Read Before LightingOperating Fireplace LightingRemote Operation Manual Lighting ProcedureTo Turn OFF GAS To Appliance OpTIONAL Hand-HeldThermostat Model HRC200 On/Off Model HRC100Main burner Inspecting BurnersOptional Blower Operation Pilot Flame PatternCleaning Maintenance Inspecting BurnersBurner Injector Holder and Pilot Air Inlet Hole Logs Cleaning MaintenanceWiring Diagram SpecificationsObserved Problem Possible Cause Remedy TroubleshootingDiagram, TroubleshootingStalling Logs, Statement above Gas leak. See WarningParts Under Warranty Replacement PartsService Hints Technical ServiceIllustrated Parts Breakdown Log Base Assembly Models VSGF33NRC and VSGF33PRCParts List Fireplace mOdels VSGF33NRC and VSGF33PRC Illustrated Parts BreakdownParts List Equipment Shutoff Valve GA5010 AccessoriesReceiver and HAND-HELD Thermostat Remote Control KIT HRC200 Receiver and HAND-HELD Remote Control KIT HRC100Accessories WALL-MOUNT ON/OFF SwitchWALL-MOUNT Thermostat 119304-01A 119304-01A Warranty Information Keep this WarrantyLimited Warranty VENT-FREE GAS Fireplace