C. Install the Termination Cap

Note: To protect against the effect of corrosion on those parts exposed to the weather, the termination cap can be painted with a rust-resistant paint.

WARNING

Fire Risk

The minimum overlap of cap to pipe MUST be met or chimney may separate from cap.

Separation allows sparks, heat and embers to escape.

Install the chimney sections up through the chase enclosure and refer to termination cap instructions.

TR11/TR444 Round Termination Cap

TR11T/TR442 Round Telescoping Termination Cap

Assemble

Termination

storm collar

Cap

around extended

 

termination cap

 

pipe

 

once cap is

 

installed.

Do NOT

 

Caulk gaps between

block air

holes

storm collar & pipe,

Storm

and storm collar

Collar

& chase top.

3 clip brackets.

 

Slip over chase collar

 

and attach with screws

 

provided.

Collar

 

2 in. (51 mm)

14 1/2 in. (368 mm)

Minimum Height

Maximum

 

Chase Top

 

Chase

Termination

Cap

Slip

storm collar

around chimney pipe

before termination cap pipe is snapped into the chimney pipe.

Caulk gaps between

Storm

storm collar & pipe,

Collar

and storm collar

 

& chase top.

 

Collar

 

2 in. (51 mm)

Chimney

Do NOT

block air holes

6 in. (153 mm) Minimum top of chase to top of chimney pipe

Chimney

Pipe

Termination cap pipe and chimney section must overlap 1-1/2 in. (38 mm)

Figure 6.5 Installing a TR11T/TR442 Round Telescoping Termina- tion Cap

ST1175/ST475 Square Termination Cap

Minimum Height

Pipe

 

Chase Top

 

Flange

Termination Cap

Place waterproof caulk or sealer under each flange of the termination cap and on top of each screw to help prevent leaks.

The last section of pipe must stop between 2 in. (51

Chase

Termination cap pipe and chimney section must be snapped together to maintain an overlap of 1-1/2 in. (38 mm).

Figure 6.4 Installing a TR11/TR444 Round Termination Cap

Collar

2 in. (51 mm)

Minimum Height

Chase Top

Chimney

Pipe

mm) above the top of the

chase and 4 3/4 in. (121

mm) below the top of the chase.

2 in. (51 mm) maximum

4 3/4 in. (121 mm) maximum

Chase

Termination cap pipe and chimney section must overlap 1-1/2 in. (38 mm)

Figure 6.6 Installing an ST1175/ST475 Square Termination Cap

20 Outdoor Lifestyles by Hearth & Home Technologies Inc. • Montana US-CAN4039-156 Rev K 7/11

Image 20
Contents Hot glass will cause burns Fire RiskModel Listing Label Information/LocationSerial Number Grate Table of Contents Not intended for use as a primary heat source Listing and Code ApprovalsAppliance Certification Design and Installation Considerations Getting StartedMoisture Resistance Typical Fireplace SystemFire Risk Explosion Risk Tools and Supplies NeededInspect Fireplace and Components Freestanding Installations see Figure Framing and ClearancesSelecting Fireplace Location Exterior Walls see FigureEnclosed Fireplace Clearances Clearances to Combustible MaterialsSidewalls/Surrounds Frame the FireplaceChimney Requirements Sharp Edges Asphyxiation Risk Installation of FireplaceInstall the Dual Cooling Air Kit Secure the Fireplace Position the FireplaceChimney Assembly Height of Chimney ComponentsUsing Offsets/Returns Chimney Offset/ReturnInstall the Ceiling Firestops Assemble the Chimney SectionsInstall the Attic Insulation Shield Double-check the Chimney AssemblySecure the Chimney  in./19 mm in lengthComplete the Enclosure Chimney TerminationChase Top Mark the Exit Point of the RoofInstall the Termination Cap ST1175/ST475 Square Termination CapTCT1175 Terra Cotta Cap Gas Code, Ansi Z223.1 AccessoriesGas Log/Lighter Provisions Finishing Hearth ExtensionGlass Doors Finishing MaterialMantel Operating Instructions General InformationOutside Air Clear Space Near the FireplaceFlue Damper FirescreenGrate Wood FuelStarting a Fire Troubleshooting Diagnostics and Problem SolvingMaintenance and Servicing the Fireplace Chimney Inspection/CleaningDisposal of Ashes Firebox RefractoryMaintenance Task List When cleaning glass doorClean Chimney FireFireplace Dimensions Reference MaterialsFireplace Components DescriptionChimney Components Catalog #Assembled Diameter 17 in./432 mm Height 24 in./610 mm 15-3/4 400 mm Woodburning Termination Cap 635 x 635 mm 584 x 584 mm 737 x 737 mmD. Service Parts MONTANA-36, MONTANA-36HService Parts MONTANA-42, MONTANA-42HThis page intentionally left blank This page intentionally left blank Warranty Coverage Limited Warranty This warranty is void ifRO N a CO ISD D