Hearth and Home Technologies 42, 36 owner manual Finishing Material, Mantel, Glass Doors

Page 24

B. Finishing Material

Combustible Material

Material which is made of or surfaced with wood, compressed paper, plant fibers, plastics, or any material capable of igniting and burning, whether flame proofed or not, plastered or not plastered.

Non-Combustible Material

Material which will not ignite and burn. Such materials are those consisting entirely of steel, iron, brick, tile, concrete, slate, glass or plasters, or any combination thereof.

Non-Combustible Sealant Material

Sealants which will not ignite and burn: Rutland, Inc. Fireplace Mortar #63, Rutland 76R, Nuflex 304, GE RTV106 or GE RTV116 (or equivalent).

After completing the framing and applying the facing material (drywall) over the framing, a bead of non-combustible seal- ant must be used to close off any gaps at the top and sides between the fireplace and facing to prevent cold air leaks. Large gaps can be bridged with fiberglass rope gasket.

Only non-combustible materials may be used to cover the black metal fireplace front.

WARNING

Fire Risk

Maintain clearances.

Use only non-combustible material below standoffs, material such as cement board is acceptable.

Framing or finishing material used on the front of, or in front of, the appliance closer than the minimums listed, must be constructed entirely of noncombustible materials (i.e., steel studs, concrete board, etc.).

C. Mantel

A combustible mantel may be positioned no lower than 12 in. (305 mm) above the top of the fireplace opening. The combustible mantel may have a maximum depth of 12 in. (305 mm), Combustible trim pieces that project no more than 1‑1/2 in. (38 mm) from the face of the fireplace can be placed no closer than 6 in. (152 mm) from the top of the fireplace opening. See Figure 8.4. Combustible trim must not cover the metal surfaces of the fireplace. This mantel clearance is in accordance with Section 7-3.3.3 of ANSI/ NFPA211.

D. Sidewalls/Surrounds

Adjacent combustible side walls must be located a minimum of 12 in. (305 mm) from the fireplace opening. If you are us- ing a decorative surround constructed of combustible ma- terial, it must be located within the shaded area defined in Figure 8.5. Short stub walls are also acceptable if they are contained within the shaded area.

E. Glass Doors

This fireplace has been tested and listed for use with doors as specified in Section 12.B. Fireplace Components. Please refer to the manual packed with each set of doors for instal- lation instructions.

WARNING

Fire Risk

Do NOT obstruct air inlet or outlet grilles.

Do NOT modify grilles.

Modifying or covering grilles could cause temperature rise and fire hazard.

Finishing materials must not interfere with:

Air flow through grilles or louvers

Operation of louvers or doors

Access for service

 

12 in. (305 mm)

 

max.

 

1-1/2 in. (38 mm) max.

Mantel

Header

 

Standoff

12 in. (305 mm)

min.

 

Top of Fireplace Opening

6 in. (152 mm) min.

Figure 8.4 Mantel Specifications

 

BRICK

4 in./10.2 cm

FLUSH FRONT

FRONT

 

 

14-3/8 in./36.5 cm

A

9-3/4 in./24.8 cm

50 deg.

B

39 deg.

12 in.

12 in.

30.5 cm

30.5 cm

Cat #

A

B

MONTANA-36 & 36H

36 in./91.4 cm

42 in./106.7 cm

MONTANA-42 & 42H

42 in./106.7 cm 48 in./121.9 cm

Figure 8.5 Sidewalls/Surrounds

WARNING

Fire Risk

Finish all edges and fronts to clearances and specifications.

Metal fireplace front may be covered with non-combustible material only.

Do NOT overlap combustible materials onto fireplace front.

Install combustible materials up to specified clearances on top front and side edges.

Seal joints between the finished wall and fireplace top and sides using only a 300° F minimum sealant.

24 Outdoor Lifestyles by Hearth & Home Technologies Inc. • Montana US-CAN4039-156 Rev K 7/11

Image 24
Contents Hot glass will cause burns Fire RiskListing Label Information/Location Serial Number GrateModel Table of Contents Listing and Code Approvals Appliance CertificationNot intended for use as a primary heat source Design and Installation Considerations Getting StartedMoisture Resistance Typical Fireplace SystemTools and Supplies Needed Inspect Fireplace and ComponentsFire Risk Explosion Risk Freestanding Installations see Figure Framing and ClearancesSelecting Fireplace Location Exterior Walls see FigureEnclosed Fireplace Clearances Clearances to Combustible MaterialsSidewalls/Surrounds Frame the FireplaceChimney Requirements Installation of Fireplace Install the Dual Cooling Air KitSharp Edges Asphyxiation Risk Secure the Fireplace Position the FireplaceChimney Assembly Height of Chimney ComponentsUsing Offsets/Returns Chimney Offset/ReturnInstall the Ceiling Firestops Assemble the Chimney SectionsInstall the Attic Insulation Shield Double-check the Chimney AssemblySecure the Chimney  in./19 mm in lengthComplete the Enclosure Chimney TerminationChase Top Mark the Exit Point of the RoofInstall the Termination Cap ST1175/ST475 Square Termination CapTCT1175 Terra Cotta Cap Accessories Gas Log/Lighter ProvisionsGas Code, Ansi Z223.1 Finishing Hearth ExtensionFinishing Material MantelGlass Doors Operating Instructions General InformationOutside Air Clear Space Near the FireplaceFlue Damper FirescreenGrate Wood FuelStarting a Fire Troubleshooting Diagnostics and Problem SolvingMaintenance and Servicing the Fireplace Chimney Inspection/CleaningDisposal of Ashes Firebox RefractoryMaintenance Task List When cleaning glass doorClean Chimney FireFireplace Dimensions Reference MaterialsFireplace Components DescriptionChimney Components Catalog #Assembled Diameter 17 in./432 mm Height 24 in./610 mm 15-3/4 400 mm Woodburning Termination Cap 635 x 635 mm 584 x 584 mm 737 x 737 mmD. Service Parts MONTANA-36, MONTANA-36HService Parts MONTANA-42, MONTANA-42HThis page intentionally left blank This page intentionally left blank Warranty Coverage Limited Warranty This warranty is void ifRO N a CO ISD D