Hearth and Home Technologies CASTLEWOOD 42 Complete the Enclosure, Install the Termination Cap

Page 17

6Complete the Enclosure

A. Chimney Termination

Chimney Termination Requirements (see Fig- ure 6.1)

Must have a cap approved and listed for this fireplace system

Must not be located where it will become plugged by snow or other material

Must terminate at least 3ft (914 mm) about the roof and at least 2 ft (610mm) above any portion of the roof within 10 ft. (305mm)

Must be located away from trees or other structures

WARNING

Fire Risk

Must maintain 2 in. (51 mm) air clearance to insulation and other combustible materials.

C. Install the Termination Cap

Note: To protect against the effect of corrosion on those parts exposed to the weather, the termination cap can be painted with a rust-resistant paint.

WARNING

Fire Risk

The minimum overlap of cap to pipe MUST be met or chimney may separate from cap.

Separation allows sparks, heat and embers to escape.

Install the chimney sections up through the chase enclosure and refer to termination cap instructions.

NOTE: TR11/TR444 Round Termination Cap and TR11T/ TR442 Round Telescoping Termination Cap not recom- mended for Installations less than 20 feet.

B. Chase Top

A metal chase top is required to seal the top of the chase around the chimney pipe. The top should include a turn- down and drip edge to prevent water from seeping into the chase. Provide a 1/8 in. (3 mm) gap around the flue pipe and slope the top downward away from the penetration.

ST1175/ST475 Square Termination Cap

All seams must be caulked to prevent leaks.

A chase installation must use a chase top. Chase tops are available from your HHT dealer or may be field constructed.

Attach the chase top to the top of the chase.

2 in. (51 mm) Collar on Chase Top

Slope Downward

Turn-down

Drip Edge

.018 (26 ga) min. Galvanized Chase Top

Figure 6.1 Field Constructed Chase Top Specification

Flange

Termination Cap

Collar

2 in. (51 mm)

Minimum Height

Chase Top

Chimney

Pipe

Place waterproof caulk or sealer under each flange of the termination cap and on top of each screw to help prevent leaks.

The last section of pipe must stop between 2 in. (51

mm)above the top of the chase and 4 3/4 in. (121

mm) below the top of the chase.

2 in. (51 mm) maximum

4 3/4 in. (121 mm) maximum

Chase

Termination cap pipe and chimney section must overlap 1-1/2 in. (38 mm)

Figure 6.2 Installing an ST1175/ST475 Square Termination Cap

Outdoor Lifestyles by Hearth & Home Technologies Inc. • 4070-300 Rev C • 4/11

17

Image 17 Contents
Fire Risk Hot glass will cause burnsNumber Listing Label Information/LocationGrate Table of Contents Appliance Certification Listing and Code ApprovalsNot intended for use as a primary heat source Do not overfireGetting Started Grate Inspect Fireplace and ComponentsFirescreen Cooling AirFraming and Clearances Freestanding Installations see FigureSelecting Fireplace Location Exterior Walls see FigureFreestanding Installation Clearances Frame the Fireplace Sidewalls/SurroundsChimney Requirements Secure the Fireplace Position the Fireplace Installation of FireplaceLevel the Fireplace Place the Protective Metal Hearth Strips Install Cooling Air Hoods Height of Chimney Components Chimney AssemblyAssemble the Chimney Sections Using Offsets/Returns Complete the Enclosure Install the Termination CapChase Top ST1175/ST475 Square Termination CapTCT1175 Terra Cotta Cap Installing a TCT1175 Square Termination CapInstall Side Molded Brick Panel Installation of Molded Brick PanelMortar Optional Grate Install ScreensGas Log/Lighter Provisions AccessoriesGas Code, Ansi Z223.1 Asphyxiation Risk= 1/k x inches of thickness FinishingHearth Extension Non-combustible Raised Hearth Extension FramingFraming Material Equivalent insulationFlush Hearth Extension Framing Non-combustible SealantUse only non-combustible framing material below standoffs Finishing MaterialStandoffs MantelGeneral Information Operating InstructionsFire Risk Smoke Risk Clear Space Near the FireplaceGlass Doors Firewood Wood FuelStarting a Fire Diagnostics and Problem Solving TroubleshootingDisposal of Ashes Chimney Inspection/Cleaning Maintenance and Servicing the FireplaceWhen cleaning glass door Maintenance Task ListClean Chimney FireReference Materials Fireplace DimensionsOptional Components Catalog # Chimney Components330 mm 51 mm 15-3/4 400 mm Termination capsODCASTLEWD-42 Service Parts ListHerringbone Molded Brick Panel At DepotTraditional Molded Brick Panel Warranty Coverage This warranty is void if Limited WarrantyRO N a CO ISD D