6Complete the Enclosure
A. Chimney Termination
Chimney Termination Requirements (see Fig- ure 6.1)
•Must have a cap approved and listed for this fireplace system
•Must not be located where it will become plugged by snow or other material
•Must terminate at least 3ft (914 mm) about the roof and at least 2 ft (610mm) above any portion of the roof within 10 ft. (305mm)
•Must be located away from trees or other structures
WARNING
Fire Risk
•Must maintain 2 in. (51 mm) air clearance to insulation and other combustible materials.
C. Install the Termination Cap
Note: To protect against the effect of corrosion on those parts exposed to the weather, the termination cap can be painted with a
WARNING
Fire Risk
•The minimum overlap of cap to pipe MUST be met or chimney may separate from cap.
Separation allows sparks, heat and embers to escape.
Install the chimney sections up through the chase enclosure and refer to termination cap instructions.
NOTE: TR11/TR444 Round Termination Cap and TR11T/ TR442 Round Telescoping Termination Cap not recom- mended for Installations less than 20 feet.
B. Chase Top
A metal chase top is required to seal the top of the chase around the chimney pipe. The top should include a turn- down and drip edge to prevent water from seeping into the chase. Provide a 1/8 in. (3 mm) gap around the flue pipe and slope the top downward away from the penetration.
ST1175/ST475 Square Termination Cap
•All seams must be caulked to prevent leaks.
•A chase installation must use a chase top. Chase tops are available from your HHT dealer or may be field constructed.
•Attach the chase top to the top of the chase.
2 in. (51 mm) Collar on Chase Top
Slope Downward
Drip Edge
.018 (26 ga) min. Galvanized Chase Top
Figure 6.1 Field Constructed Chase Top Specification
Flange
Termination Cap
Collar
2 in. (51 mm)
Minimum Height
Chase Top
Chimney
Pipe
Place waterproof caulk or sealer under each flange of the termination cap and on top of each screw to help prevent leaks.
The last section of pipe must stop between 2 in. (51
mm)above the top of the chase and 4 3/4 in. (121
mm) below the top of the chase.
2 in. (51 mm) maximum
4 3/4 in. (121 mm) maximum
Chase
Termination cap pipe and chimney section must overlap
Figure 6.2 Installing an ST1175/ST475 Square Termination Cap
Outdoor Lifestyles by Hearth & Home Technologies Inc. • | 17 |