Outdoor Unit CU-3KS19NBU Indoor Unit CS-MKS9NB4U × 1

Cooling Characteristics

(RH : 46%, Indoor fan speed : High fan) (230V, 60Hz)

(1) Low pressure performance chart

servicevalve

psig(MPaG)

174

Lo fan

 

Hi fan

 

 

HH fan

 

 

 

 

 

 

(1.2)

 

 

 

 

 

 

 

 

 

 

 

 

 

tube

 

160

 

 

 

 

 

 

wide

 

(1.1)

 

 

 

 

 

 

 

 

 

 

 

 

 

(30°C)

at

 

 

 

 

 

 

. 86°F

 

 

 

 

 

 

 

pressure

 

 

 

 

 

air

temp

 

 

146

 

 

Indoor

 

 

 

 

 

 

(27°C)

 

 

(1.0)

 

 

80°F

 

 

 

 

(24°C)

 

 

 

 

 

75°F

 

Low

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

132

 

 

 

 

 

 

 

 

(0.9)77

 

86

 

 

95

104

 

 

(25)

 

(30)

 

 

(35)

(40)

Outdoor air temperature °F (°C)

(2) Operating current performance chart

 

6

 

 

 

 

 

 

Lo fan

 

Hi fan

 

 

HH fan

(A)

5

 

 

 

 

 

 

 

 

 

 

 

current

 

 

 

 

.86°F

(30°C)

 

 

 

 

 

Operating

 

 

 

 

 

4

 

 

air

temp

 

 

 

 

 

 

 

Indoor

 

 

 

 

(27°C)

 

 

 

80°F

(24°C)

 

 

 

 

75°F

 

 

3

 

 

 

 

 

 

 

 

 

 

 

77

86

 

 

95

104

 

(25)

(30)

 

 

(35)

(40)

Outdoor air temperature °F (°C)

(3) Indoor discharge air performance chart

(°C)

Lo fan

Hi fan

 

 

 

HH fan

68.0(20)

 

 

 

 

 

°F

 

 

 

 

 

 

air temperature

64.4(18)

 

 

 

 

 

60.8(16)

 

 

. 86°F

(30°C)

 

 

 

 

Indoor

air

temp

 

 

 

 

 

 

57.2(14)

 

 

 

 

 

 

80°F

(27°C)

discharge

 

 

 

 

 

53.6(12)

 

 

 

 

(24°C)

 

 

 

75°F

 

 

 

 

50.0(10)

 

 

 

 

 

Indoor

 

 

 

 

 

46.4( 8)

 

 

 

 

 

 

77

86

 

95

 

104

 

(25)

(30)

 

(35)

 

(40)

Outdoor air temperature °F (°C)

NOTE

This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type.

Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.)

The performance is for a tubing length of 24.6ft (7.5m). If the tubing length is different, the performance chart will vary.

31

Image 31
Contents DC Inverter MULTI-SYSTEM AIR Conditioner Safety Precautions Prohibit Table of Contents Appendix a Semi-Concealed Type Wall Mounted TypeOperating Range Duct Less Type Rated Unit SpecificationsOutdoor Unit CU-3KS19NBU Indoor Unit CS-MKS9NKU ×Indoor Unit Outdoor Unit208V CU-4KS24NBU BTU/h/W Compressor Locked Rotor Amperes 20,600 CU-4KS31NBU Indoor Unit CS-MKS9NKU 4units Outdoor Unit CU-4KS31NBU 1unit 24,200 Outdoor Unit Major Component SpecificationsOutdoor Unit CU-4KS24NBU Outdoor Unit CU-4KS31NBU CU-3KS19NBU CU-4KS24NBU CU-4KS31NBU Other Component SpecificationsDimensional Data Unit inchmm 852-0-0010-20500-0 Unit inchmm 852-0-0010-20600-0 Outdoor unit Refrigerant Flow DiagramInsulation of Refrigerant Tubing Indoor unitIndoor unit Outdoor unit 1/4 Strainer Header Sub Main Compressor Accumulator Temperature Charts CU-3KS19NBU Temperature ChartsOutdoor Unit CU-3KS19NBU Indoor Unit CS-MKS7NKU × Outdoor Unit CU-3KS19NBU Indoor Unit CS-MKS9NKU × Outdoor Unit CU-3KS19NBU Indoor Unit CS-MKS12NKU × Cooling CharacteristicsOutdoor Unit CU-3KS19NBU Indoor Unit CS-MKS18NKU × Outdoor Unit CU-3KS19NBU Indoor Unit CS-MKS9NB4U × Outdoor Unit CU-3KS19NBU Indoor Unit CS-MKS12NB4U × Outdoor Unit CU-3KS19NBU Indoor Unit CS-KS18NB4UW × Outdoor Unit CU-4KS24NBU Indoor Unit CS-MKS7NKU × Temperature Charts CU-4KS24NBUOutdoor Unit CU-4KS24NBU Indoor Unit CS-MKS9NKU × Outdoor Unit CU-4KS24NBU Indoor Unit CS-MKS12NKU × Outdoor Unit CU-4KS24NBU Indoor Unit CS-MKS18NKU × Outdoor Unit CU-4KS24NBU Indoor Unit CS-MKS24NKU × Outdoor Unit CU-4KS24NBU Indoor Unit CS-MKS9NB4U × Outdoor Unit CU-4KS24NBU Indoor Unit CS-MKS12NB4U × Outdoor Unit CU-4KS24NBU Indoor Unit CS-KS18NB4UW × Temperature Charts CU-4KS31NBU Outdoor Unit CU-4KS31NBU Indoor Unit CS-MKS9NKU × Outdoor Unit CU-4KS31NBU Indoor Unit CS-MKS12NKU × Outdoor Unit CU-4KS31NBU Indoor Unit CS-MKS18NKU × Outdoor Unit CU-4KS31NBU Indoor Unit CS-MKS24NKU × Outdoor Unit CU-4KS31NBU Indoor Unit CS-MKS9NB4U × Outdoor Unit CU-4KS31NBU Indoor Unit CS-MKS12NB4U × Outdoor Unit CU-4KS31NBU Indoor Unit CS-KS18NB4UW × Indoor Outdoor Cooling CapacityCS-MKS12NB4U × Power Supply 230V Single Phase 60Hz Cooling CapacityCS-MKS9NKU × CS-KS18NB4UW + CS-MKS12NB4U + CS-MKS12NB4U 30,600 BTU/h CS-MKS9NB4U × Cooling Capacity Low Ambient 15,180 18,570 19,250 25,420 19,410 19,360 24,830 19,520 24,260 30,760 22,560 28,790 22,730 Outdoor Unit CU-3KS19NBU 8FA2-5251-11800-1 Electric Wiring DiagramsOutdoor Unit CU-4KS24NBU 8FA2-5251-11600-1 Outdoor Unit CU-4KS31NBU 8FA2-5251-11400-1 Explanation of Functions FunctionsCool DRY Fluctuation fanLow Ambient Cooling Operation Automatic frequency control Protective FunctionsCurrent Control Description of functionLow Start Current Compressor Temperature ControlCurrent control Precautions before Performing Inspection or Repair Troubleshooting Before Calling for ServiceLocation of the Error Monitor Lamps Trouble Diagnosis by Error Monitor LampsDisplay of the Error Monitor Lamps Checking the Outdoor System Work procedure Check items unit operationChecking the outdoor unit Trouble Diagnosis of Each Part Problems of Each Part and Inspection PointsCompressor Inspection Points for Each PartOutdoor control circuit board FuseCU-3KS19NBU MV0 MV1 MV2 CU-4KS24NBU MV3 CU-4KS31NBU Electric expansion valveBreaker Branch tubing temperature sensorRefrigerant gas pressure Trouble Diagnosis of Fan Motor Diagnostic procedureDiagnostic results Remedy for symptom 3 toComponents mixing proportions Characteristics of New Refrigerant R410AWhat is New Refrigerant R410A? CharacteristicsChecklist before Servicing Tools Specifically for R410A Tubing Installation ProceduresCase of Compressor Malfunction Procedure for Replacing CompressorR410A from changing Amount in the charging cylinder is less than 20%Example To prevent the compositionWelding leaking points Case Refrigerant is LeakingRecharging Use of Existing Units When Tubes are ExtendedCharging Additional Refrigerant Retro-Fitting Existing Systems852-6-4190-581-00-1 For Outdoor Unit ContentsPlease Read Before Starting ‡ 8VHWKHIODUHPHWKRGIRUFRQQHFWLQJWXELQJ Fins of the outdoor unit. You may get injuredGeneral For wall-mounted units Installation Site SelectionFor ceiling-mounted cassette units H1, H2, H3, H4 Connecting indoor unit for CU-3KS19NBU Connecting Indoor UnitsConnecting indoor unit for CU-4KS24NBU 815.88mm Locally purchased Connecting indoor unit for CU-4KS31NBU CS-MKS24NKU Back Baffle Plate for the Outdoor UnitIt is recommended to use baffle plates FrontAir Discharge Baffle Air Intake BafflePrecautions for installation CU-4KS31NBU Outer Dimensions of Outdoor UnitCU-3KS19NBU CU-4KS24NBUNever install only a single indoor unit Diagram of Outdoor Unit InstallationFlaring Procedure with a Flare Tool Installation ProcessUse of the Flaring Method Tubing Connections To 0.5 mm Adjust so that the amount of tube For ceiling-mounted cassette units Insulation of Refrigerant TubingTo prevent heat loss and wet floors due to dripping of con  For wall-mounted unitsAir Purging Finishing the Installation Air Purging with a Vacuum Pump for Test Run Adapter manual, and use the adapter correctly External diameter of service port R410A 5/16If pump-down is not possible What is pump-down?Pump-down procedure  Pump DownGeneral Precautions on Wiring Wiring InstructionsRecommended Wire Length and Diameter Disconnect switch may be required by national or local codes For Indoor Unit How to connect wiring to the terminalFor Outdoor Unit  For solid core wiring or F-cable  For stranded wiringIndoor unit C Wiring Instructions for the Outdoor UnitIndoor unit D Indoor unit BTest Run Checking tubing and wiringPerforming a test run Installation Check Sheet Connecting a Home Automation DeviceDC1111-0