Panasonic CU-4KS31NBU service manual Installation Site Selection, For wall-mounted units

Page 91

2. Installation Site Selection

Indoor unit

2-1. Indoor Unit

WARNING

AVOID:

To prevent abnormal heat generation and the possibility of fire, do not place obstacles, enclosures and grilles in front of or surrounding the air conditioner in a way that may block air flow.

Drain hose

Outside drainage

direct sunlight.

nearby heat sources that may affect performance of the unit.

areas where leakage of flammable gas may be expected.

placing or allowing any obstructions near the air conditioner inlet or outlet.

installing in rooms that contain instant-on (rapid-start) fluorescent lamps. (These may prevent the air conditioner from receiving signals.)

places where large amounts of oil mist exist.

installing in locations where there are devices that generate high-frequency emissions.

Fig. 1

For wall-mounted units

 

6" (15 cm)

2" (5 cm)

2" (5 cm)

min.

 

min.

min.

 

 

 

Front View

Fig. 2a

DO:

select an appropriate position from which every corner of the room can be uniformly air-conditioned. (High on a wall is best for wall-mounted types.)

select a location that will hold the weight of the unit.

select a location where tubing and drain hose have the shortest run to the outside. (Fig. 1)

allow room for operation and maintenance as well as unrestricted air flow around the unit. (Fig. 2a or 2b)

install the unit within the maximum elevation difference (H1, H2, H3, H4) above or below the outdoor unit and within a total tubing length (L1+L2+L3, L1+L2+L3+L4) from the outdoor unit as detailed in Table 3 and Fig. 3a.

For ceiling-mounted cassette units

3.3 ft.

3.3 ft.

(1m)

(1m)

3.3 ft.

3.3 ft.3.3 ft. (1m)

(1m)

(1m)

Fig. 2b

CAUTION

 

 

 

 

INDOOR

 

Tubing length (L1)

 

 

 

 

 

 

 

 

 

UNIT (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INDOOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT (2)

 

 

 

 

 

Elevation

 

 

 

 

L2

 

 

 

 

 

OUTDOOR

 

 

 

 

 

 

difference

(H1)

 

 

 

 

H2

 

 

 

 

 

 

 

 

UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H4

 

 

 

INDOOR

 

L4

 

INDOOR

 

H3

 

 

 

 

 

UNIT (4)

 

 

UNIT (3)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

‡$LUGHOLYHU\IURPDFHLOLQJ mounted cassette unit will be degraded if the distance from the floor to the ceiling is greater than 10 ft. (3 m).

‡)RUVWDEOHRSHUDWLRQRIWKH air conditioner, do not install wall-mounted units less than 5' (1.5 m) from floor level. (Fig. 3b)

Indoor unit

Minimum height from floor level

5' (1.5 m)

Wall

Floor level

Fig. 3a

Fig. 3b

5

Image 91
Contents DC Inverter MULTI-SYSTEM AIR Conditioner Safety Precautions Prohibit Table of Contents Appendix a Semi-Concealed Type Wall Mounted TypeOperating Range Duct Less Type Rated Unit SpecificationsOutdoor Unit CU-3KS19NBU Indoor Unit CS-MKS9NKU ×Indoor Unit Outdoor Unit208V CU-4KS24NBU BTU/h/W Compressor Locked Rotor Amperes 20,600 CU-4KS31NBU Indoor Unit CS-MKS9NKU 4units Outdoor Unit CU-4KS31NBU 1unit 24,200 Outdoor Unit Major Component SpecificationsOutdoor Unit CU-4KS24NBU Outdoor Unit CU-4KS31NBU CU-3KS19NBU CU-4KS24NBU CU-4KS31NBU Other Component SpecificationsDimensional Data Unit inchmm 852-0-0010-20500-0 Unit inchmm 852-0-0010-20600-0 Outdoor unit Refrigerant Flow DiagramInsulation of Refrigerant Tubing Indoor unitIndoor unit Outdoor unit 1/4 Strainer Header Sub Main Compressor Accumulator Temperature Charts CU-3KS19NBU Temperature ChartsOutdoor Unit CU-3KS19NBU Indoor Unit CS-MKS7NKU × Outdoor Unit CU-3KS19NBU Indoor Unit CS-MKS9NKU × Outdoor Unit CU-3KS19NBU Indoor Unit CS-MKS12NKU × Cooling CharacteristicsOutdoor Unit CU-3KS19NBU Indoor Unit CS-MKS18NKU × Outdoor Unit CU-3KS19NBU Indoor Unit CS-MKS9NB4U × Outdoor Unit CU-3KS19NBU Indoor Unit CS-MKS12NB4U × Outdoor Unit CU-3KS19NBU Indoor Unit CS-KS18NB4UW × Outdoor Unit CU-4KS24NBU Indoor Unit CS-MKS7NKU × Temperature Charts CU-4KS24NBUOutdoor Unit CU-4KS24NBU Indoor Unit CS-MKS9NKU × Outdoor Unit CU-4KS24NBU Indoor Unit CS-MKS12NKU × Outdoor Unit CU-4KS24NBU Indoor Unit CS-MKS18NKU × Outdoor Unit CU-4KS24NBU Indoor Unit CS-MKS24NKU × Outdoor Unit CU-4KS24NBU Indoor Unit CS-MKS9NB4U × Outdoor Unit CU-4KS24NBU Indoor Unit CS-MKS12NB4U × Outdoor Unit CU-4KS24NBU Indoor Unit CS-KS18NB4UW × Temperature Charts CU-4KS31NBU Outdoor Unit CU-4KS31NBU Indoor Unit CS-MKS9NKU × Outdoor Unit CU-4KS31NBU Indoor Unit CS-MKS12NKU × Outdoor Unit CU-4KS31NBU Indoor Unit CS-MKS18NKU × Outdoor Unit CU-4KS31NBU Indoor Unit CS-MKS24NKU × Outdoor Unit CU-4KS31NBU Indoor Unit CS-MKS9NB4U × Outdoor Unit CU-4KS31NBU Indoor Unit CS-MKS12NB4U × Outdoor Unit CU-4KS31NBU Indoor Unit CS-KS18NB4UW × Indoor Outdoor Cooling CapacityCS-MKS12NB4U × Power Supply 230V Single Phase 60Hz Cooling CapacityCS-MKS9NKU × CS-KS18NB4UW + CS-MKS12NB4U + CS-MKS12NB4U 30,600 BTU/h CS-MKS9NB4U × Cooling Capacity Low Ambient 15,180 18,570 19,250 25,420 19,410 19,360 24,830 19,520 24,260 30,760 22,560 28,790 22,730 Outdoor Unit CU-3KS19NBU 8FA2-5251-11800-1 Electric Wiring DiagramsOutdoor Unit CU-4KS24NBU 8FA2-5251-11600-1 Outdoor Unit CU-4KS31NBU 8FA2-5251-11400-1 Explanation of Functions FunctionsCool DRY Fluctuation fanLow Ambient Cooling Operation Automatic frequency control Protective FunctionsCurrent Control Description of functionLow Start Current Compressor Temperature ControlCurrent control Precautions before Performing Inspection or Repair Troubleshooting Before Calling for ServiceLocation of the Error Monitor Lamps Trouble Diagnosis by Error Monitor LampsDisplay of the Error Monitor Lamps Checking the Outdoor System Work procedure Check items unit operationChecking the outdoor unit Trouble Diagnosis of Each Part Problems of Each Part and Inspection PointsCompressor Inspection Points for Each PartOutdoor control circuit board FuseCU-3KS19NBU MV0 MV1 MV2 CU-4KS24NBU MV3 CU-4KS31NBU Electric expansion valveBreaker Branch tubing temperature sensorRefrigerant gas pressure Trouble Diagnosis of Fan Motor Diagnostic procedureDiagnostic results Remedy for symptom 3 toComponents mixing proportions Characteristics of New Refrigerant R410AWhat is New Refrigerant R410A? CharacteristicsChecklist before Servicing Tools Specifically for R410A Tubing Installation ProceduresCase of Compressor Malfunction Procedure for Replacing CompressorR410A from changing Amount in the charging cylinder is less than 20%Example To prevent the compositionWelding leaking points Case Refrigerant is LeakingRecharging Use of Existing Units When Tubes are ExtendedCharging Additional Refrigerant Retro-Fitting Existing Systems852-6-4190-581-00-1 For Outdoor Unit ContentsPlease Read Before Starting ‡ 8VHWKHIODUHPHWKRGIRUFRQQHFWLQJWXELQJ Fins of the outdoor unit. You may get injuredGeneral For wall-mounted units Installation Site SelectionFor ceiling-mounted cassette units H1, H2, H3, H4 Connecting indoor unit for CU-3KS19NBU Connecting Indoor UnitsConnecting indoor unit for CU-4KS24NBU 815.88mm Locally purchased Connecting indoor unit for CU-4KS31NBU CS-MKS24NKU Back Baffle Plate for the Outdoor UnitIt is recommended to use baffle plates FrontAir Discharge Baffle Air Intake BafflePrecautions for installation CU-4KS31NBU Outer Dimensions of Outdoor UnitCU-3KS19NBU CU-4KS24NBUNever install only a single indoor unit Diagram of Outdoor Unit InstallationFlaring Procedure with a Flare Tool Installation ProcessUse of the Flaring Method Tubing Connections To 0.5 mm Adjust so that the amount of tube For ceiling-mounted cassette units Insulation of Refrigerant TubingTo prevent heat loss and wet floors due to dripping of con  For wall-mounted unitsAir Purging Finishing the Installation Air Purging with a Vacuum Pump for Test Run Adapter manual, and use the adapter correctly External diameter of service port R410A 5/16If pump-down is not possible What is pump-down?Pump-down procedure  Pump DownGeneral Precautions on Wiring Wiring InstructionsRecommended Wire Length and Diameter Disconnect switch may be required by national or local codes For Indoor Unit How to connect wiring to the terminalFor Outdoor Unit  For solid core wiring or F-cable  For stranded wiringIndoor unit C Wiring Instructions for the Outdoor UnitIndoor unit D Indoor unit BTest Run Checking tubing and wiringPerforming a test run Installation Check Sheet Connecting a Home Automation DeviceDC1111-0