(7) Branch tubing temperature sensor
Check that the sensor is securely contained in the thermostat holder.
(8) Breaker
Check whether or not the breaker has been tripped.
Check that the breakers and fuses used are of the specified capacity.
Check that the breaker and its line are exclusive for A/C use.
(9) Refrigerant gas pressure
Start a COOL test run, and messure the temperatures of the A/C intake air and discharge air. Compare the values with the performance charts.
If the values are higher than the performance charts:
Check for refrigerant shortage or blockage of the refrigerant circuit.
<Assessment of refrigerant shortage >
1.The pressure in the
2.There is little condensation on the indoor heart exchanger, which overall appears dry.
<Distinguishing between refrigerant shortage and refrigerant circuit blockage >
If the pressure in the
The problem may be a blockage of the refrigerant circuit.
1.Check that there is no internal leakage inside the
At the
2.Check that the electric expansion valve is not blocked. Check as described on the preceding page.
77