Chapter 6: Maintaining Your Filtered Enclosure
•External Alarm allows an external signal to sound the alarm, such as a sash open switch, or a “fail” signal from the building airflow system.
•Alarm Disable allows an external signal to prevent a “low” airflow alarm from occurring.
•Night Setback allows an external signal to prevent a “low” airflow alarm from occurring (not any different from Alarm Disable above other than the terminology.)
Contact Labconco for ordering information on this special PCB.
Calibration
1.Ensure the flow switch and alarm circuit board are installed and operational.
2.Allow the enclosure to operate for at least two minutes.
3.If factory installed, the monitor will alarm at 60±10 fpm with the inflow velocity set at 90±10 fpm.
4.To change the factory setting, set the inflow velocity required by your Safety Officer to the desired alarm condition using the speed control adjustment procedure outlined in Chapter 6.
5.Once the alarm condition is set, use a small screwdriver to turn the adjustment screw on the airflow switch counterclockwise (facing the screw) until the “low” airflow red LED lights and the audible flow alarm sounds.
6.Adjust the inflow velocity to the nominal operating point required by your Safety Officer.
7.Over time the HEPA filter will load and eventually slow the inflow velocity. Once the alarm condition is met, simply increase the speed control outlined in Chapter 6 or replace the HEPA filter if the speed control is maximized.
8.The table below lists typical alarm conditions based on normal operating conditions. Typical alarm conditions are set at face velocities of 10 to 30 feet per minute below the normal operating conditions due to supply air and exhaust air fluctuations, as well as room air cross drafts. Consult your Safety Officer for proper operating speeds.
Enclosure Operating | Alarm Condition Set Point |
Speed | Speed |
100 ± 10 fpm | |
90 ± 10 fpm | |
80 ± 10 fpm | |
70 ± 10 fpm | |
60 ± 10 fpm | 50 fpm |
51