Ductwork Connections

Examples of poor and good fan-to-duct connections

are shown below. Airflow out of the fan

 

 

 

 

 

should be directed straight or curve

 

 

 

 

 

the same direction as the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

fan wheel rotates. Poor

 

 

 

 

 

 

 

 

tion

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

 

 

duct installation will result

 

 

 

R

o

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in low airflow and

other

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

system effects.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POOR

 

 

 

 

 

 

tion

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Length of Straight Duct

 

 

 

 

 

 

 

 

 

 

 

a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

o

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GOOD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Recommended Discharge Duct Size and Length

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Size

 

 

 

Blower

 

Duct Size

 

 

 

 

Straight Duct

 

 

 

 

Size

 

 

 

 

 

 

Length

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ERCH-HP 20

 

 

 

 

9

 

 

 

 

 

14 x 14

 

 

 

 

 

 

36

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ERCH-HP 45

 

 

 

 

10

 

 

 

 

20 x 20

 

 

 

 

 

 

36

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ERCH-HP 55

 

 

 

 

12

 

 

 

 

20 x 20

 

 

 

 

 

 

36

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ERCH-HP 90

 

 

 

 

15

 

 

 

 

28 x 28

 

 

 

 

 

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

All dimensions shown in inches.

Recommended duct sizes are based on velocities across the cfm range of each model at approximately 800 feet per minute (FPM) at minimum airflow and up to 1600 fpm at maximum airflow.

Recommended duct sizes are only intended to be a guide and may not satisfy the requirements of the project. Refer to plans for appropriate job specific duct size and/or velocity limitations.

Straight duct lengths were calculated based on 100% effective duct length requirements as prescribed in AMCA Publication 201. Calculated values have been rounded up to nearest foot.

Rail Mounting / Layout

Rails designed to handle the weight of the unit should be positioned as shown on the diagram (rails by others).

Make sure that rail positioning does not interfere with the supply air discharge opening or the exhaust air intake opening on the unit. Avoid area dimensioned “B” below.

Rails should run the width of the unit and extend beyond the unit a minimum of 12 inches on each side.

• Set unit on rails.

AirOutdoorHoodIntake

Supply/Exhaust

Opening

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Side view of unit on rails

 

 

 

 

 

 

Isometric view of unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rail Mounting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Size

 

 

 

A

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ERCH-HP 20

 

 

 

5.0

 

 

 

41.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ERCH-HP 45

 

 

 

7.0

 

 

 

41.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ERCH-HP 55

 

 

 

5.5

 

 

 

53.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ERCH-HP 90

 

 

 

6.0

 

 

 

59.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

All dimensions are in inches.

Exhaust Weatherhood

The exhaust weatherhood is shipped separately as a kit with its own instructions.

Model ERCH-HP Energy Recovery Unit 11

Image 11
Contents Model ERCH-HP General Safety InformationHandling Inspection and Maintenance during StorageReceiving UnpackingTable of Contents Models and Capacities Product OverviewCoils SubassembliesLocation of components in the module will vary Heat Pump ModuleUnit Weights and Recommended Roof Opening InstallationDimensional Data ERCH-HP 20 ERCH-HP Service ClearancesLifting Lugs LiftingSet the Unit Lift Roof Curb Mounting Curb Outside Dimensions and WeightsInstall Ductwork Exhaust Weatherhood Ductwork ConnectionsRail Mounting / Layout Start-Up Unit Voltage Imbalance Pre-Start-Up ChecklistStart-Up Procedure Unit Start-Up Checklist Electrical Information Condensate Drain Trap Discharge Air Temperature SensorPlumbing / Piping Overview Day Timer or On/Off Switch Optional Remote Control PanelWiring Schematics Indicator Lights powered by the ER UnitOptional Control Center Components Optional Frost Control TimerElectrical Controls Variable Frequency Drive VFD Phase MonitorOptional Economizer Dirty Filter Sensor Optional Rotation SensorStart-Up Adjust the Air SealsEnergy Wheel Sequence of OperationEnergy Wheel Maintenance Heat Pump Overview Energy Wheel TroubleshootingFactory-Installed Heat Pump System Components Heat Pump Controls Refrigeration System Schematic Typical Operating Conditions Intelligent Reset Unit Protection Module UPM Fault IndicationsLockout Reset FX05 Furnace Controller Troubleshooting Controller AlarmsDDC Controller Measured Airflow Troubleshooting AirflowTroubleshooting Unit Design AirflowResistance Troubleshooting Note Troubleshooting Refrigeration CircuitTwo hours. Recheck for open circuit Check bulb for contact Check entering air wet bulb conditions Worn oil pump Replace the oil pump Dampers Routine MaintenanceMaintenance Frequency Maintenance Procedures LubricationFan Bearings Fan MotorsFan Wheel and Fasteners Coil Maintenance Internal Filter MaintenanceExternal Filter Maintenance Maintenance Log Warranty

473501 specifications

Greenheck Fan 473501 is a significant player in the world of ventilation solutions, specifically designed to meet the increasing demands for efficiency and effectiveness in air movement. This commercial-grade fan is particularly noted for its high performance and reliability, making it a top choice for various applications, ranging from industrial settings to larger commercial spaces.

One of the main features of the Greenheck 473501 is its energy-efficient design. It is engineered to minimize energy consumption while maximizing airflow, allowing users to achieve optimal performance without incurring high utility bills. The fan is equipped with a powerful motor that not only ensures consistent airflow but also contributes to its overall longevity and durability.

The fan boasts an impressive air performance rating, which is crucial for environments that require precise temperature and humidity control. With adjustable airflow settings, users can customize the fan’s operation to suit specific needs, whether that means circulating air in a warehouse or exhaust in a manufacturing facility.

Another standout characteristic is the fan's robust construction. Built with corrosion-resistant materials, the Greenheck 473501 is ideal for use in harsh environments, where exposure to moisture and other elements could compromise lesser fans. The design also incorporates noise-reducing technologies, making it suitable for settings where quiet operation is essential, such as schools, hospitals, and office buildings.

In terms of installation, the Greenheck 473501 is designed for versatility. It can be easily integrated into various ventilation systems, whether for new constructions or upgrades to existing infrastructure. Its compact footprint allows for convenient placement without sacrificing performance.

Furthermore, Greenheck offers extensive support and resources for this model, ensuring users have access to the information necessary for optimal operation, maintenance, and any potential troubleshooting.

Overall, the Greenheck Fan 473501 represents a harmonious blend of efficiency, durability, and flexibility, making it an ideal choice for those seeking a high-quality ventilation solution that meets contemporary environmental standards while delivering reliable performance across diverse applications.