Greenheck Fan 473501 manual Unit Protection Module UPM Fault Indications, Lockout Reset

Page 27

Unit Protection Module (UPM) Fault Indications

Each unit includes one Unit Protection Module (UPM) printed circuit board and each UPM has two LED indictor lights.

LED

LED Fault Indication

Color

 

Lockout Reset

A hard lockout can be reset by turning the unit thermostat off and then back on when the “RESET” dip switch is set to “Y” or by shutting off unit power at the circuit breaker when the “RESET” dip switch is set to “R”.

Green

Power LED indicates 18-30 VAC present at

the board

 

 

 

 

 

 

 

Dual or

# of

 

 

Single

Status

 

blinks

 

Compressor

 

 

 

 

 

 

 

 

 

 

1

High pressure lockout

 

 

Compressor 1

 

 

 

 

 

 

 

 

 

2

Low pressure lockout

 

 

Compressor 1

 

 

 

 

 

3

High pressure lockout

 

 

Compressor 2

 

 

 

 

 

 

 

 

 

4

Low pressure lockout

 

Dual

Compressor 2

 

 

 

Compressor

 

 

 

5

Freeze sensor lockout

 

 

 

 

(optional item)

 

 

 

 

 

 

 

 

 

 

Condensate overflow

Red

 

6

in coil drain pan

 

 

 

(optional item)

 

 

 

Brownout AC voltage

 

 

7

to R and C terminal

 

 

 

below 18 VAC

 

 

 

 

 

 

1

High pressure lockout

 

 

 

 

 

 

2

Low pressure lockout

 

 

 

 

 

 

3

Freeze sensor lockout

 

 

(optional item)

 

Single

 

 

 

 

 

 

Condensate overflow

 

Compressor

 

 

4

in coil drain pan

 

 

 

 

 

(optional item)

 

 

 

 

 

 

 

Brownout AC voltage

 

 

5

to R and C terminals

 

 

 

below 18 VAC

 

 

 

 

Intelligent Reset

If a fault condition is initiated, the five minute delay on break time period and the random start timer is initiated and the unit will restart after these delays expire. During this period the fault LED will indicate the cause of the fault. If the fault condition occurs 2 or 4 times (depending on 2 or 4 setting for Lockout dip switch) before 60 minutes, the unit will go into a hard lockout and requires a manual lockout reset. A single condensate overflow fault will cause the unit to go into a hard lockout immediately, and will require a manual lockout reset.

Your UPM board will come from the factory with the following default settings:

Default Settings

Freeze

NO

 

 

Temp

35°

 

 

Lockout

2

 

 

Reset

T

 

 

Alarm

CONT

 

 

Test

NO

 

 

Hot/Dry Alarm

HOT

 

 

Model ERCH-HP Energy Recovery Unit 27

Image 27
Contents Model ERCH-HP General Safety InformationHandling Inspection and Maintenance during StorageReceiving UnpackingTable of Contents Models and Capacities Product OverviewCoils SubassembliesLocation of components in the module will vary Heat Pump ModuleInstallation Dimensional DataUnit Weights and Recommended Roof Opening ERCH-HP 20 ERCH-HP Service ClearancesLifting Lugs LiftingRoof Curb Mounting Curb Outside Dimensions and Weights Install DuctworkSet the Unit Lift Ductwork Connections Rail Mounting / LayoutExhaust Weatherhood Start-Up Unit Pre-Start-Up Checklist Start-Up ProcedureVoltage Imbalance Unit Start-Up Checklist Electrical Information Discharge Air Temperature Sensor Plumbing / Piping OverviewCondensate Drain Trap Day Timer or On/Off Switch Optional Remote Control PanelWiring Schematics Indicator Lights powered by the ER UnitOptional Control Center Components Timer Electrical ControlsOptional Frost Control Phase Monitor Optional EconomizerVariable Frequency Drive VFD Dirty Filter Sensor Optional Rotation SensorStart-Up Adjust the Air SealsEnergy Wheel Sequence of OperationEnergy Wheel Maintenance Energy Wheel Troubleshooting Factory-Installed Heat Pump System ComponentsHeat Pump Overview Heat Pump Controls Refrigeration System Schematic Typical Operating Conditions Unit Protection Module UPM Fault Indications Lockout ResetIntelligent Reset Troubleshooting Controller Alarms DDC ControllerFX05 Furnace Controller Measured Airflow Troubleshooting AirflowTroubleshooting Unit Design AirflowResistance Troubleshooting Note Troubleshooting Refrigeration CircuitTwo hours. Recheck for open circuit Check bulb for contact Check entering air wet bulb conditions Worn oil pump Replace the oil pump Dampers Routine MaintenanceMaintenance Frequency Maintenance Procedures LubricationFan Motors Fan Wheel and FastenersFan Bearings Internal Filter Maintenance External Filter MaintenanceCoil Maintenance Maintenance Log Warranty

473501 specifications

Greenheck Fan 473501 is a significant player in the world of ventilation solutions, specifically designed to meet the increasing demands for efficiency and effectiveness in air movement. This commercial-grade fan is particularly noted for its high performance and reliability, making it a top choice for various applications, ranging from industrial settings to larger commercial spaces.

One of the main features of the Greenheck 473501 is its energy-efficient design. It is engineered to minimize energy consumption while maximizing airflow, allowing users to achieve optimal performance without incurring high utility bills. The fan is equipped with a powerful motor that not only ensures consistent airflow but also contributes to its overall longevity and durability.

The fan boasts an impressive air performance rating, which is crucial for environments that require precise temperature and humidity control. With adjustable airflow settings, users can customize the fan’s operation to suit specific needs, whether that means circulating air in a warehouse or exhaust in a manufacturing facility.

Another standout characteristic is the fan's robust construction. Built with corrosion-resistant materials, the Greenheck 473501 is ideal for use in harsh environments, where exposure to moisture and other elements could compromise lesser fans. The design also incorporates noise-reducing technologies, making it suitable for settings where quiet operation is essential, such as schools, hospitals, and office buildings.

In terms of installation, the Greenheck 473501 is designed for versatility. It can be easily integrated into various ventilation systems, whether for new constructions or upgrades to existing infrastructure. Its compact footprint allows for convenient placement without sacrificing performance.

Furthermore, Greenheck offers extensive support and resources for this model, ensuring users have access to the information necessary for optimal operation, maintenance, and any potential troubleshooting.

Overall, the Greenheck Fan 473501 represents a harmonious blend of efficiency, durability, and flexibility, making it an ideal choice for those seeking a high-quality ventilation solution that meets contemporary environmental standards while delivering reliable performance across diverse applications.