Greenheck Fan 473501 manual Troubleshooting Refrigeration Circuit, Troubleshooting Note

Page 31

Troubleshooting – Refrigeration Circuit

TROUBLESHOOTING NOTE

Before any components are changed on the refrigeration system, the cause of the failure must be identified. Further problems will exist unless the true cause or problem is identified and corrected.

IMPORTANT

Do not release refrigerant to the atmosphere! If required service procedures include the adding or removing of refrigerant, the service technician must comply with all federal, state and local laws. The procedures discussed in this manual should only be performed by an EPA Certified Technician.

NOTE: Unit is equipped with a phase loss/phase reversal control. If system does not start, check phase of electrical supply.

Symptom

Possible Cause

Corrective Action

 

 

 

 

Open disconnect switch or circuit breaker.

Close switch and / or breaker.

 

 

 

 

Compressor contactor not closing.

Check voltage to contactor coil, transformer, slave

 

relay, system. Replace parts as necessary.

 

 

 

 

 

 

Blown fuse or tripped breaker.

Check for reason and repair. Replace fuse after

 

correcting problem.

 

 

 

 

 

 

Low line voltage.

Check line voltage. If more than 10% from

 

compressor marking, correcting is necessary.

 

 

 

 

 

 

 

Motor thermal protector automatically resets.

 

Compressor motor protector open.

Allow time (2 hrs.) for compressor to cool down so

Compressor

protector will reset. Restart and check for reason

 

 

overheat occurred.

will not run

 

 

 

or

 

Check motor for open circuit, short circuit,

does not

Compressor defective.

grounded windings or burn out.

try to start

Compressor may be seized; check refrigerant.

 

 

 

If necessary, replace compressor.

 

 

 

 

 

If manual reset (high pressure), reset switch.

 

 

(Switch opens at 600 psi and will not reset above

 

High or low pressure switch open or defective.

420 psi for R-410A.

 

 

If auto reset (low pressure) does not reset and

 

 

everything else is OK, replace switch.

 

 

 

 

Open room thermostat or control

Check room temperature. If temperature is proper,

 

(no cooling required).

wait for thermostat to close.

 

 

 

 

Loose wiring.

Check all wire terminals and tighten as necessary.

 

 

 

 

Low refrigerant charge.

Check refrigerant pressures.

Compressor starts

 

 

 

Check for dirty evaporator coil, dirty filters,

but cuts out on low

Airflow restricted.

dampers closed, iced evaporator coil, improper

pressure

 

belt, check motor amps, check duct design.

 

 

 

Low pressure

 

Check refrigerant pressure, check and adjust

Restriction in refrigerant line.

thermal expansion valve. If not functioning properly,

switch activates

 

check for pressure drop across the filter drier.

at 50 PSIG for R-410A

 

 

 

 

Defective low pressure switch.

Replace.

 

 

 

Always have a completed Pre Start-Up Checklist and Unit Start-Up Checklist prior to requesting parts or service information.

Model ERCH-HP Energy Recovery Unit 31

Image 31
Contents Model ERCH-HP General Safety InformationHandling Inspection and Maintenance during StorageReceiving UnpackingTable of Contents Models and Capacities Product OverviewCoils SubassembliesLocation of components in the module will vary Heat Pump ModuleDimensional Data InstallationUnit Weights and Recommended Roof Opening ERCH-HP 20 ERCH-HP Service ClearancesLifting Lugs LiftingInstall Ductwork Roof Curb Mounting Curb Outside Dimensions and WeightsSet the Unit Lift Rail Mounting / Layout Ductwork ConnectionsExhaust Weatherhood Start-Up Unit Start-Up Procedure Pre-Start-Up ChecklistVoltage Imbalance Unit Start-Up Checklist Electrical Information Plumbing / Piping Overview Discharge Air Temperature SensorCondensate Drain Trap Day Timer or On/Off Switch Optional Remote Control PanelWiring Schematics Indicator Lights powered by the ER UnitOptional Control Center Components Electrical Controls TimerOptional Frost Control Optional Economizer Phase MonitorVariable Frequency Drive VFD Dirty Filter Sensor Optional Rotation SensorStart-Up Adjust the Air SealsEnergy Wheel Sequence of OperationEnergy Wheel Maintenance Factory-Installed Heat Pump System Components Energy Wheel TroubleshootingHeat Pump Overview Heat Pump Controls Refrigeration System Schematic Typical Operating Conditions Lockout Reset Unit Protection Module UPM Fault IndicationsIntelligent Reset DDC Controller Troubleshooting Controller AlarmsFX05 Furnace Controller Measured Airflow Troubleshooting AirflowTroubleshooting Unit Design AirflowResistance Troubleshooting Note Troubleshooting Refrigeration CircuitTwo hours. Recheck for open circuit Check bulb for contact Check entering air wet bulb conditions Worn oil pump Replace the oil pump Dampers Routine MaintenanceMaintenance Frequency Maintenance Procedures LubricationFan Wheel and Fasteners Fan MotorsFan Bearings External Filter Maintenance Internal Filter MaintenanceCoil Maintenance Maintenance Log Warranty

473501 specifications

Greenheck Fan 473501 is a significant player in the world of ventilation solutions, specifically designed to meet the increasing demands for efficiency and effectiveness in air movement. This commercial-grade fan is particularly noted for its high performance and reliability, making it a top choice for various applications, ranging from industrial settings to larger commercial spaces.

One of the main features of the Greenheck 473501 is its energy-efficient design. It is engineered to minimize energy consumption while maximizing airflow, allowing users to achieve optimal performance without incurring high utility bills. The fan is equipped with a powerful motor that not only ensures consistent airflow but also contributes to its overall longevity and durability.

The fan boasts an impressive air performance rating, which is crucial for environments that require precise temperature and humidity control. With adjustable airflow settings, users can customize the fan’s operation to suit specific needs, whether that means circulating air in a warehouse or exhaust in a manufacturing facility.

Another standout characteristic is the fan's robust construction. Built with corrosion-resistant materials, the Greenheck 473501 is ideal for use in harsh environments, where exposure to moisture and other elements could compromise lesser fans. The design also incorporates noise-reducing technologies, making it suitable for settings where quiet operation is essential, such as schools, hospitals, and office buildings.

In terms of installation, the Greenheck 473501 is designed for versatility. It can be easily integrated into various ventilation systems, whether for new constructions or upgrades to existing infrastructure. Its compact footprint allows for convenient placement without sacrificing performance.

Furthermore, Greenheck offers extensive support and resources for this model, ensuring users have access to the information necessary for optimal operation, maintenance, and any potential troubleshooting.

Overall, the Greenheck Fan 473501 represents a harmonious blend of efficiency, durability, and flexibility, making it an ideal choice for those seeking a high-quality ventilation solution that meets contemporary environmental standards while delivering reliable performance across diverse applications.