2. Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum of 500 microns and vacuum gage capable of accurately measuring the vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water.

1.Vacuum pressure should pull down below 500 microns in 2 minutes.

2.Evacuate system for 30 minutes.

3.Shut valve to vacuum pump off.

4.After 10 minutes read pressure.

If pressure remains below 1000 microns, system is ready.

If pressure is between 1000 and 2000 microns continue evacuation for additional 30 minutes. If pressure is above 2000 microns, there is a leak in the system.

3.Triple Evacuation Method

The triple evacuation method should only be used when vacuum pump is only capable of pumping down to a 28” Hg. vacuum and system does not contain any liquid water.

1.Pump system down to 28”Hg. and allow pump to continue operating for an additional 15 minutes.

2.Close high and low side valves on gauge manifold and shut off vacuum pump.

3.Connect a nitrogen cylinder and regulator to system and open until system pressure is 2 psig.

4.Close service valve and allow system to stand for 1 hour. This will allow dry nitrogen to diffuse throughout the system absorbing moisture.

5.Complete this procedure until system until it is able to hold a deep vacuum then release charge into system.

4.Final Tubing Check

IMPORTANT: Check to be certain factory tubing on both indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.

7. Operation characteristics

CAUTION:

1.Operation of air conditioner beyond the above conditions may cause certain protections to occur.

2.Room relative humidity should be less than 80%. If the air conditioner operates in excess of this value, the surface of the air conditioner may cause condensation. If condensation does occur, place the vertical air louver to it’s maximum angle (vertically to the floor) and set the fan to high speed.

18

Image 18
Contents Inverter Single Zone Ductless Mini Split Heat Pump Contents Precaution Safety Precaution Installation  For installation, always contact the dealer  Caution  Use two or more people to lift and transport the product  Keep level even when installing the product Operational  Do not block the inlet or outlet of air flow Do not drink the water drained from the product Function Anti-freeze protection in coolingOutdoor unit Compressor delay Dimension Indoor UnitModel Dimension mm Outdoor UnitRefrigerant Cycle Diagram Indoor OutdoorWiring Diagrams VMH09SC-1 A-VMH12SC-1 VMH18SC-1 Installation details Pipe length and the elevation Single Zone V Series Inverter SystemPressure Test & Evacuation System Evacuation and ChargingOperation characteristics Electronic function AbbreviationDisplay function Main Protection Operation Modes and Functions Preheat modeFan only mode Preheat terminationCooling Mode Compressor running rules Frequency decreases Holds Model CurrentCondenser high temperature T3 protection Outdoor fan rulesIndoor fan running rules Evaporator low temperature T2 protection Heating Mode Compressor running rulesT1-Ts-ΔT +5.0 +4.5 +3.5 +3.0 +2.5 +2.0 +1.5 +1.0 +0.5 I1HEAT I2HEAT I3HEAT Outdoor fan running rulesVMH12SC-1 Indoor fan rulesUnit TEL0 TEL1 VMH09SC-1 VMH18SC-1Defrost mode: Defrost Actions For 9K and 12K unit For 18K and 24K unit High evaporator coil temp.T2 protection Auto-modeDehumidify mode Forced operation functionTimer function Sleep function modeIonizer Clean Air function Auto-Restart functionAutomatic front panel function Troubleshooting SafetyIndoor Unit Error Display Diagnosis and SolutionEeprom parameter error diagnosis and solution VMH Series E3 Indoor or E7 Outdoor Igbt over current protection diagnosis and solution VMH Series 29 P3 Error Low Ambient Protection Inverter compressor drive error diagnosis and solutionKey parts checking Position Resistance ValueVMH Series Some frequently-used R-T data for T1, T2, T3 and T4 sensor 2012