Service Manual | VMH Series | Heat Controller, Inc. |
|
|
|
After A/C starts up, the compressor will run at the Fmax frequency for 7 minutes according to outdoor ambient temp. During the 7 minutes, frequency limitation is active.
7 minutes later, compressor running frequency will be controlled as below:
|
|
°F | °C |
41 | (+5.0) |
40 | (+4.5) |
38 | (+3.5) |
37 | (+3.0) |
37 | (+2.5) |
36 | (+2.0) |
35 | (+1.5) |
34 | (+1.0) |
33 | (+0.5) |
|
|
While
Temp. zone | A | B | C | D | E | F | G |
Frequency | F10 | F9 | F8 | F7 | F5 | F3 | F4 |
ΔT=32°F/0°C as default.
Note:
When
F:Keeps the current frequency.
G:Decreases the frequency to the lower level F1.
H:Runs at F1 for 1h. (If