9.29 P3 ERROR – Low Ambient Protection

If the outdoor temperature remains at 5°F(-15°C) for an hour, the compressor will turn off and the error code “P3” will be displayed on the indoor unit. Once the compressor has been off for at least an hour and the temperature outside is equal to or greater than 10.4°F(-12°C) for at least ten minutes, the system will restart. Additionally if the outside temperature reaches at least 41°F(5°C) for at least ten minutes, the system will restart without the needed 1 hour compressor off time required.

P4:

9.2.10 Inverter compressor drive error diagnosis and solution

Is the connection of compressor good? Is the wiring sequence right? The voltage range proper?

Yes

Replace the outdoor PCB

No

No

Reconnect and retry

Replace inverter compressor.

9.2.9 Zero crossing check resistance or inverter compressor, it is .7error

Alarm signal when the main chip can’t detect over-zero signal. When such failure occurs, the main control board must have fault.

Check power supply and

connections

Correct power supply or

correct connections

Indoor PCB defective

41

Image 41
Contents Inverter Single Zone Ductless Mini Split Heat Pump Contents  Installation PrecautionSafety Precaution  For installation, always contact the dealer  Caution  Operational  Keep level even when installing the product Use two or more people to lift and transport the product  Do not block the inlet or outlet of air flow Do not drink the water drained from the product Anti-freeze protection in cooling FunctionOutdoor unit Compressor delay Indoor Unit DimensionOutdoor Unit Model Dimension mmIndoor Outdoor Refrigerant Cycle DiagramWiring Diagrams VMH09SC-1 A-VMH12SC-1 VMH18SC-1 Installation details Single Zone V Series Inverter System Pipe length and the elevationSystem Evacuation and Charging Pressure Test & EvacuationOperation characteristics Display function Electronic functionAbbreviation Main Protection Fan only mode Preheat modeOperation Modes and Functions Preheat terminationCooling Mode Compressor running rules Model Current Frequency decreases HoldsIndoor fan running rules Condenser high temperature T3 protectionOutdoor fan rules Heating Mode Compressor running rules Evaporator low temperature T2 protectionT1-Ts-ΔT +5.0 +4.5 +3.5 +3.0 +2.5 +2.0 +1.5 +1.0 +0.5 Outdoor fan running rules I1HEAT I2HEAT I3HEATUnit TEL0 TEL1 VMH09SC-1 Indoor fan rulesVMH12SC-1 VMH18SC-1Defrost mode: Defrost Actions For 9K and 12K unit For 18K and 24K unit Auto-mode High evaporator coil temp.T2 protectionForced operation function Dehumidify modeSleep function mode Timer functionAutomatic front panel function Ionizer Clean Air functionAuto-Restart function Safety TroubleshootingEeprom parameter error diagnosis and solution Indoor Unit Error DisplayDiagnosis and Solution VMH Series E3 Indoor or E7 Outdoor Igbt over current protection diagnosis and solution VMH Series Inverter compressor drive error diagnosis and solution 29 P3 Error Low Ambient ProtectionPosition Resistance Value Key parts checkingVMH Series Some frequently-used R-T data for T1, T2, T3 and T4 sensor 2012