Service Manual | VMH Series | Heat Controller, Inc. |
|
|
|
9.1 Indoor Unit Error Display
Display | LED STATUS | |
|
|
|
E0 | EEPROM parameter error | |
|
|
|
E1 | Indoor / outdoor units communication protection | |
|
|
|
E2 | ||
|
|
|
E3 | Indoor fan speed out of control | |
|
|
|
E5 | Open or short circuit of outdoor temperature sensor | |
|
|
|
E6 | Open or short circuit of room or evaporator temperature sensor | |
|
|
|
E7 | Outdoor fan speed out of control | |
|
|
|
P0 | IBM malfunction or IGBT | |
|
|
|
P1 | Over voltage or too low voltage protection | |
|
|
|
P2 | Temperature protection of compressor top. | |
|
|
|
P3 | 1 outdoor temp below | |
|
|
|
P4 | Inverter compressor drive error | |
|
|
|
Note: E4 & P3: Reserved function
9.2 Diagnosis and Solution
EO:
9.2.1 EEPROM parameter error diagnosis and solution
Shut off the power supply and turn it on 5s later
Does EO code clear
Is the EEPROM chip plugged in indoor PCB well?
No
Correct the connection
Replace the main PCB of indoor unit