6.3 Pressure Test & Evacuation

Air and moisture in the refrigerant system have undesirable effects as below:

Pressure in the system rises.

Operating current rises.

Cooling or heating efficiency drops.

Moisture in the refrigerant circuit may freeze and block capillary tubing.

Refrigerant lines and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. The alternate triple evacuation method may be used if the procedure outlined is followed.

1. System Evacuation and Charging

(Indoor unit)

(Liquid side)

(Outdoor unit)

 

 

 

 

Two-way valve

 

 

Close

 

(Gas side)

 

Manifold valve

Three-way valve

Close

500 Microns

 

Lo

Hi

Low Side

HI Side

Charge hose

Charge hose

Vacuum

 

pump

 

Vacuum

 

pump

 

1)Completely tighten the flare nuts of the indoor and outdoor units, connect manifold gauge low side hose to low side service valve.

2)Connect the manifold gauge charge hose to the vacuum pump.

3)Fully open the low side of manifold gauge.

4)Start vacuum pump.

5)Evacuate using either deep vacuum or triple evacuation method.

6)After evacuation is complete, fully close the low side of manifold gauge and shut off vacuum pump.

7)The factory charge contained in the outdoor unit is good for up to 16.5 ft. of line length. For line set lengths over 16.5 ft., adjust charge according to chart in section 6.2.

8)Disconnect charge hose from low side service valve.

9)Fully open both high and low side service valves and securely tighten caps.

17

Image 17
Contents Inverter Single Zone Ductless Mini Split Heat Pump Contents  Installation PrecautionSafety Precaution  For installation, always contact the dealer  Caution  Operational  Keep level even when installing the product Use two or more people to lift and transport the product  Do not block the inlet or outlet of air flow Do not drink the water drained from the product Anti-freeze protection in cooling FunctionOutdoor unit Compressor delay Indoor Unit DimensionOutdoor Unit Model Dimension mmIndoor Outdoor Refrigerant Cycle DiagramWiring Diagrams VMH09SC-1 A-VMH12SC-1 VMH18SC-1 Installation details Single Zone V Series Inverter System Pipe length and the elevationSystem Evacuation and Charging Pressure Test & EvacuationOperation characteristics Display function Electronic functionAbbreviation Main Protection Fan only mode Preheat modeOperation Modes and Functions Preheat terminationCooling Mode Compressor running rules Model Current Frequency decreases HoldsIndoor fan running rules Condenser high temperature T3 protectionOutdoor fan rules Heating Mode Compressor running rules Evaporator low temperature T2 protectionT1-Ts-ΔT +5.0 +4.5 +3.5 +3.0 +2.5 +2.0 +1.5 +1.0 +0.5 Outdoor fan running rules I1HEAT I2HEAT I3HEATUnit TEL0 TEL1 VMH09SC-1 Indoor fan rulesVMH12SC-1 VMH18SC-1Defrost mode: Defrost Actions For 9K and 12K unit For 18K and 24K unit Auto-mode High evaporator coil temp.T2 protectionForced operation function Dehumidify modeSleep function mode Timer functionAutomatic front panel function Ionizer Clean Air functionAuto-Restart function Safety TroubleshootingEeprom parameter error diagnosis and solution Indoor Unit Error DisplayDiagnosis and Solution VMH Series E3 Indoor or E7 Outdoor Igbt over current protection diagnosis and solution VMH Series Inverter compressor drive error diagnosis and solution 29 P3 Error Low Ambient ProtectionPosition Resistance Value Key parts checkingVMH Series Some frequently-used R-T data for T1, T2, T3 and T4 sensor 2012