Heat Controller VMH12SC-1, VMH24SC-1, VMH09SC-1, VMH18SC-1 service manual Main Protection

Page 20

Service Manual

VMH Series

Heat Controller, Inc.

 

 

 

8.3 Main Protection

8.3.1 Three Minute Time Delay at restart for compressor.

1 minute delay for 1st time start-up and 3 minute delay for others.

8.3.2 Temperature protection of compressor top.

Protector cuts off compressor for 30 seconds and restarts after 3 minute delay.

8.3.3 Temperature protection of compressor discharge.

When the compressor discharge temperature increases, the compressor frequency will be limited as indicated below:

Compressor discharge temp. T5>239°F/115°C for 5 seconds, compressor stops.

If T5<239°F/115°C, decreases compressor frequency to the lower level every 3 minutes.

T5>194°F/90°C, cancels the frequency limit control and restarts the compressor.

8.3.4 Fan Speed is out of control.

When indoor fan speed is lower than 300 RPM for 50 second, the whole unit stops and LED displays error code E3, and the unit will not resume operation automatically.

8.3.5 Inverter module Protection.

Inverter module protection has a protection function against current, voltage and temperature. If any of these conditions occur, the corresponding code will display on indoor unit LED and A/C will stop. Once the code is cleared unit will restart after the 3 min delay.

8.3.6 Indoor fan delayed open function

When the system starts up, the louver will be active immediately and the indoor fan will open 10 seconds later.

If the system is in heating mode, the anti-cold wind function has priority.

8.3.7Compressor preheating functions. Preheat conditions:

If the main relay closes, T437°F/3°C and the unit is powered on, or T437°F/3°C and compressor has stopped over 3 hours, the compressor heating cable will operate.

20

Image 20
Contents Inverter Single Zone Ductless Mini Split Heat Pump Contents  Installation PrecautionSafety Precaution  For installation, always contact the dealer  Caution  Keep level even when installing the product  Operational Use two or more people to lift and transport the product  Do not block the inlet or outlet of air flow Do not drink the water drained from the product Function Anti-freeze protection in coolingOutdoor unit Compressor delay Dimension Indoor UnitModel Dimension mm Outdoor UnitRefrigerant Cycle Diagram Indoor OutdoorWiring Diagrams VMH09SC-1 A-VMH12SC-1 VMH18SC-1 Installation details Pipe length and the elevation Single Zone V Series Inverter SystemPressure Test & Evacuation System Evacuation and ChargingOperation characteristics Display function Electronic functionAbbreviation Main Protection Preheat mode Fan only modeOperation Modes and Functions Preheat terminationCooling Mode Compressor running rules Frequency decreases Holds Model CurrentIndoor fan running rules Condenser high temperature T3 protectionOutdoor fan rules Evaporator low temperature T2 protection Heating Mode Compressor running rulesT1-Ts-ΔT +5.0 +4.5 +3.5 +3.0 +2.5 +2.0 +1.5 +1.0 +0.5 I1HEAT I2HEAT I3HEAT Outdoor fan running rulesIndoor fan rules Unit TEL0 TEL1 VMH09SC-1VMH12SC-1 VMH18SC-1Defrost mode: Defrost Actions For 9K and 12K unit For 18K and 24K unit High evaporator coil temp.T2 protection Auto-modeDehumidify mode Forced operation functionTimer function Sleep function modeAutomatic front panel function Ionizer Clean Air functionAuto-Restart function Troubleshooting SafetyEeprom parameter error diagnosis and solution Indoor Unit Error DisplayDiagnosis and Solution VMH Series E3 Indoor or E7 Outdoor Igbt over current protection diagnosis and solution VMH Series 29 P3 Error Low Ambient Protection Inverter compressor drive error diagnosis and solutionKey parts checking Position Resistance ValueVMH Series Some frequently-used R-T data for T1, T2, T3 and T4 sensor 2012